F-Gas English Low GWP

Všetky otázky
HFC | Flammable | CO₂ | NH₃
Ľahké otázky | Stredne ťažké otázky | Ťažké otázky

1

Stredne ťažká

What process takes place in the condenser of a refrigeration system?


The refrigerant absorbs heat from the surroundings and evaporates
Hot vapour discharged by the compressor is desuperheated, condensed, and the resulting liquid is slightly subcooled
The secondary fluid (glycol, water) condenses while the refrigerant evaporates
The refrigerant rejects only the heat generated in the compressor

2

Stredne ťažká

What mainly determines the condensing temperature of an air-cooled condenser?


The ambient (inlet) air temperature
The evaporating temperature
The superheat
The compressor discharge temperature

3

Stredne ťažká

Why does heat flow from the condenser to the surroundings?


Because HFC refrigerants attract heat from the surroundings
Because the compressor pushes heat directly into the surroundings
Because the pressure in the condenser is lower than ambient
Because the condensing temperature is higher than the ambient temperature, and heat flows spontaneously from a warmer to a colder body (second law of thermodynamics)

4

Stredne ťažká

What should you mainly pay attention to when operating a condenser?


That the inlet air temperature is lower than the outlet air temperature
The colour of the condenser casing
That the outlet air temperature is higher than the condensing temperature
Its general condition and the cleanliness of the heat-exchange surfaces

5

Stredne ťažká

What criteria should be considered when selecting a suitable condenser?


Only the size and number of fans
Only own experience and the dimensions
The required capacity of the condenser and the technical specifications declared by the manufacturer
Fan noise, connection diameters and colour

6

Stredne ťažká

How do contaminants (dust, particulates, deposits) affect the performance and efficiency of heat exchange surfaces in condensers?


Contaminants do not significantly affect the efficiency and effectiveness of the heat exchange surfaces in condensers.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause a reduction in condensing pressure.
Contaminants increase the heat transfer area and reduce the condensing pressure.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause an increase in condensing temperature and pressure, which in turn leads to a reduction in the condenser’s efficiency.

7

Stredne ťažká

How does the capacity of an air-cooled condenser change when it becomes dirty?


It increases
It increases because the fan speed rises
It remains unchanged
It decreases

8

Stredne ťažká

What is the main consequence of heavy frost on an air-cooling evaporator?


An increase in condenser subcooling
A rise in the cooled-air temperature with no effect on capacity
Reduced heat transfer and airflow, resulting in a drop in cooling capacity and evaporating temperature
A rise in evaporating pressure

9

Stredne ťažká

What happens when the evaporation temperature drops?


The discharge temperature decreases.
The condenser fan speed increases.
The compressor’s cooling capacity decreases.
The compressor’s cooling capacity increases.

10

Stredne ťažká

When is natural (off-cycle, air) defrosting possible?


Only in freezer rooms below −18 °C
When the air passing through the cooler is above 0 °C
Never – electric heaters must be used in every air cooler
Only in coolers fitted with speed-controlled fans

11

Stredne ťažká

When does frost form on the surface of an air-cooling evaporator?


Only when the system runs continuously
Only when the room air temperature falls below 0 °C
Always, in every air cooler
When the evaporator surface temperature is below 0 °C and below the dew point of the air

12

Stredne ťažká

In extensive pipework systems, flash gas (secondary evaporation) in the liquid line can be prevented by…


…additional subcooling of the liquid
…insulating the discharge line between the compressor and the condenser
…using smaller-diameter pipes
…increasing the length of the liquid line

13

Stredne ťažká

How does hot gas defrosting of the evaporator work?


We switch on the gas heater directed at the evaporator.
This involves reversing the direction of rotation of the compressor.
Heated vapour (hot gas) from the compressor is directed into the evaporator piping.
We swap the outlet and inlet sides of the evaporator.

14

Stredne ťažká

What is the function of the evaporator in a refrigeration system?


It transfers heat from the medium being cooled to the boiling refrigerant.
It ensures that the refrigerant is superheated over the largest possible heat exchange surface area.
It cools the refrigerant.
It evaporates the water flowing through the evaporator.

15

Stredne ťažká

What condition must electric heaters for evaporator defrosting meet?


Heat from the heaters must be carried by the running fans
They must have good thermal contact with the heat-exchange surface (e.g. inserted in the fin block)
They must be located beneath the evaporator
They must be in direct contact with the refrigerant

16

Stredne ťažká

Refrigerant distributor:


ensures even distribution of the refrigerant to the individual sections of the condenser.
acts as a buffer for the refrigerant in the event that the pressure upstream of the expansion valve is exceeded.
ensures the even distribution of the refrigerant discharged by compressors connected in parallel.
ensures an even distribution of the refrigerant to the individual sections of the evaporator.

17

Stredne ťažká

What defrosting methods are used for air coolers?


Electric, hot gas, water spray and natural (at positive temperatures)
Electric only – other methods are not permitted in refrigeration
Natural only – other methods are ineffective and uneconomic
Only by switching off the fans with the compressor running

18

Stredne ťažká

The boiling point of a liquid rises when the pressure above the liquid…


…varies depending on the ambient temperature
…falls
…remains constant
…rises

19

Stredne ťažká

MOP in thermostatic expansion valves stands for:


minimum flow opening.
maximum operating pressure.
self-cleaning of the valve in the event of moisture in the refrigerant freezing.
maximum pressure switch protection.

20

Stredne ťažká

The function of a thermostatic expansion valve (TEV) is:


to maintain a constant compressor suction pressure
to meter refrigerant into the evaporator according to the superheat of the vapour leaving the evaporator
to maintain a constant condensing pressure
to adjust the evaporating pressure in the condenser

21

Stredne ťažká

What type of compressor motor can be used with a capillary tube?


A low-speed motor
A low-starting-torque motor (pressures equalise during standstill)
A high-starting-torque motor must be used
An electronically commutated motor

22

Stredne ťažká

What does a thermostatic expansion valve control?


The mass flow of refrigerant fed into the evaporator
The condensing pressure
The temperature in the cold room
The discharge temperature

23

Stredne ťažká

What does the manufacturer state as the factory setting of a thermostatic expansion valve?


the static superheat of the valve.
the degree of refrigerant expansion.
the superheat value during valve operation.
the degree to which the valve is filled with refrigerant liquid.

24

Stredne ťažká

Where is a new or repaired system with an expansion valve and liquid receiver charged?


Anywhere – the charging point does not matter
Through the capillary tube outlet during normal system operation
In the liquid phase on the high-pressure side, with the compressor stopped
In the liquid phase into the compressor suction, with the compressor running

25

Stredne ťažká

What does a thermostatic or electronic expansion valve control?


The evaporating pressure – closing below the set point
The amount of refrigerant fed to the evaporator according to superheat
Subcooling, by adjusting condensing pressure
The compressor speed

26

Stredne ťažká

What does the MOP function of thermostatic expansion valves mean?


The valve maintains a constant condensing pressure
The valve limits subcooling
The valve prevents motor overheating by injecting liquid into the compressor
The valve limits the maximum evaporating (suction) pressure, protecting the compressor motor from overload, e.g. after defrost

27

Stredne ťažká

The lower the liquid temperature upstream of the expansion valve, (at the same mass flow)…


…the lower qo, with Qo unchanged
…the higher the specific refrigerating effect qo [kJ/kg] and the higher the cooling capacity Qo
…the lower qo and the lower energy efficiency
…the lower qo and the lower Qo

28

Stredne ťažká

How should the MOP point of an expansion valve be selected relative to the highest normal evaporating temperature?


Higher by approx. 20 K
About 7 K lower than that temperature
A few kelvin higher (approximately 7 K)
Freely – the MOP value is irrelevant

29

Stredne ťažká

What is the function of the suction pressure regulator?


It limits the suction pressure and protects the compressor from excessively high suction pressure.
It prevents a drop in suction pressure and, if necessary, shuts down the refrigeration system.
To maintain the suction pressure at the highest possible level.
It maintains the evaporation pressure at a constant level.

30

Stredne ťažká

What is the function of the valve regulating water flow through the condenser?


To maintain the condensing pressure at the highest possible level.
To maintain the water temperature at the highest level.
To maintain the condensing pressure at a constant level.
To maintain the condensing pressure at the lowest possible level.

31

Stredne ťažká

The use of a refrigerant distributor requires a thermostatic expansion valve ...


... with internal pressure equalisation.
... with a MOP function.
... with external pressure equalisation.
... with an adsorption-type sensor filling.

32

Stredne ťažká

What properties should good insulation materials have?


High thermal conductivity
Low thermal conductivity (and low water absorption, vapour tightness)
The ability to absorb large amounts of moisture
An antistatic coating

33

Stredne ťažká

When is refrigerant vapour superheated?


When its temperature is higher than the saturation temperature corresponding to its pressure
When the compressor motor temperature rises excessively
When the pressure on the discharge side is higher than on the suction side
When the evaporating temperature is lower than the ambient temperature

34

Stredne ťažká

How can you check whether the liquid refrigerant is reaching the expansion valve without vapour bubbles?


We check using a pressure gauge fitted on the discharge side of the compressor.
We are unable to check this.
We check this using a sight glass.
We check using a liquid pressure gauge.

35

Stredne ťažká

Where does the liquid line run?


Between the evaporator and the compressor
Between the evaporator and the suction-line heat exchanger
Between the compressor and the condenser
From the condenser (liquid receiver) to the expansion valve

36

Stredne ťažká

What is the function of the liquid receiver in a refrigeration system?


To store refrigerant and compensate for changes in the circulating charge as the heat load varies
To act as a reserve when the required charge is unknown
To collect liquid refrigerant and excess oil
To further subcool the condensed refrigerant

37

Stredne ťažká

What is the purpose of the liquid receiver during service work?


It collects excess oil circulating in the system
It allows pump-down and temporary storage of the refrigerant
It further subcools the refrigerant before the expansion valve
It is a reserve when the installer does not know the required charge

38

Stredne ťažká

Where should the liquid receiver be installed?


It should be fitted between the compressor and the condenser.
It should be fitted after the evaporator.
It should be installed downstream of the condenser, upstream of the expansion valve.
It should be fitted just before the compressor.

39

Stredne ťažká

What is the function of the suction pressure regulator fitted to the suction pipe when the compressor starts up?


It closes when the suction pressure upstream of the compressor drops.
It opens when the suction pressure upstream of the compressor drops.
It regulates the evaporation pressure.
It regulates the condensing pressure.

40

Stredne ťažká

The use of microchannel heat exchangers, compared with conventional heat exchangers made of copper tubes and fins, results in:


A reduction in refrigerant charge and, typically, higher energy efficiency.
An increase in the amount of refrigerant in the system and an increase in condensing pressure.
There is no effect whatsoever on either the amount of refrigerant or energy efficiency.
A reduction in the system’s energy efficiency.

41

Stredne ťažká

Which refrigerants belong to the HFC group?


R134a, R404A, R507A, R410A.
R134a, R32, R22, R507A, R290.
R22, R401A.
R11, R12, R502.

42

Stredne ťažká

Which refrigerants belong to the HFO group?


R134a, R404A.
R22, R12.
R134a, R290.
R1234yf, R1234ze(E).

43

Stredne ťažká

What are the characteristics of R410A refrigerant compared to R407C refrigerant?


The saturation pressure of R407C refrigerant is much higher than that of R410A.
The saturation pressure of both refrigerants is roughly the same.
The saturation pressure of R407C is 150% higher than that of R410A.
The saturation pressure of R410A refrigerant is higher than that of R407C.

44

Stredne ťažká

What does the TEWI indicator define?


The ability of the ozone layer to recover
The impact of a refrigerant on the ozone layer
The global warming potential of a gas relative to CO₂ over a 100-year horizon
Total Equivalent Warming Impact: the sum of direct emissions (leakage and refrigerant losses at disposal) and indirect emissions (CO₂ from generating the energy consumed by the equipment) over its lifetime

45

Stredne ťažká

What are the characteristics of R452A compared with R404A?


Both are azeotropic and have no temperature glide
It is a flammable and toxic single-component HFC
It is a non-flammable (A1) HFC/HFO blend with properties similar to R404A and a GWP about 45% lower
The temperature glide of R452A is half that of R404A

46

Stredne ťažká

What distinguishes R1234yf from R134a?


Higher toxicity
It is mildly flammable (class A2L), whereas R134a is non-flammable (A1)
A higher critical temperature
A higher normal boiling point

47

Stredne ťažká

How does CO₂ (R744) compare with R134a?


It has identical properties and is a drop-in replacement for R134a
Unlike R134a, it is an azeotropic mixture
Its temperature glide is 7 K greater than that of R134a
It has a lower critical temperature, much higher operating pressures and a much higher volumetric cooling capacity (smaller compressors and pipes)

48

Stredne ťažká

Which of the following is NOT a fluorinated greenhouse gas?


Perfluorocarbons (PFCs).
Sulphur hexafluoride (SF6).
Hydrofluorocarbons (HFCs).
Carbon dioxide (CO₂).

49

Stredne ťažká

What is the greenhouse effect?


Clouds reflect ultraviolet radiation, which makes the air near the surface warmer
Dust in the atmosphere reflects sunlight, lowering the average surface temperature
Greenhouse gases absorb and re-emit the Earth's infrared radiation, warming the lower atmosphere
Chlorine compounds destroy stratospheric ozone, increasing UV radiation at the surface

50

Stredne ťažká

What is R1270?


n-Butane
Propene (propylene)
Isobutane
Propane

51

Stredne ťažká

How do refrigeration systems contribute to the greenhouse effect?


Indirectly (through energy consumption) and directly (through emissions of refrigerant into the atmosphere)
Only through the heat rejected by the condenser
Only through CO₂ given off by the compressor motor
Through oil emitted into the atmosphere from the condenser and filter

52

Stredne ťažká

What is the greenhouse effect?


The filtering of solar radiation by the atmosphere
The formation of a layer that traps only heat from fuel combustion in aircraft
The trapping of heat in the Earth's atmosphere, which hinders the radiation of heat into space
The absorption of solar radiation by the Earth's surface

53

Stredne ťažká

Which EU regulation is currently the primary piece of legislation governing the use of fluorinated greenhouse gases (F-gases) in the European Union?


Regulation (EU) 2024/573
Regulation (EU) 2015/1188
Directive 2009/125/EC
Regulation (EU) No 517/2014

54

Stredne ťažká

What is the main objective of Regulation (EU) 2024/573?


Standardising metal recycling standards
To reduce taxes on refrigeration equipment
Prevention of F-gas emissions and the achievement of the EU’s climate targets
To facilitate the import of electrical appliances

55

Stredne ťažká

What are the ecodesign obligations of manufacturers of refrigerating appliances?


Only using energy labels under Regulation (EU) 2024/573
Only declaring F-gas quantities under Regulation (EU) No 517/2014
Only implementing an ISO 9001 quality management system
Meeting implementing regulations (e.g. 2019/2019, 2015/1095): efficiency, spare parts, reparability

56

Stredne ťažká

What is the main objective of EU ecodesign legislation (Directive 2009/125/EC, now Regulation (EU) 2024/1781 – ESPR)?


To standardise the appearance of products in the EU
To increase sales of electrical appliances in the EU
To reduce the negative environmental impact of products by improving energy efficiency, durability and recyclability
To facilitate imports from outside the EU

57

Stredne ťažká

What is the function of a ball valve in a refrigeration system?


It measures the moisture content of the refrigerant
It regulates the temperature of the refrigerant
It prevents excessive pressure build-up in the system
Enables the refrigerant flow to be completely shut off

58

Stredne ťažká

How do certain gases contribute to the greenhouse effect?


They trap thermal radiation that the Earth would otherwise emit into space
They deplete the ozone layer, so more solar radiation reaches the surface
They heat the air through chemical reactions with atmospheric oxygen and nitrogen
They limit UV radiation reaching the Earth's surface, changing the heat balance

59

Stredne ťažká

What is the purpose of a sight glass (with moisture indicator)?


Emergency shut-off of flow
Regulating compressor pressure
Measuring condenser temperature
Visual assessment of the refrigerant condition in the liquid line (bubbles) and of system moisture

60

Stredne ťažká

What is the function of the temperature regulator in a refrigeration system?


It drains excess refrigerant into the receiver
It restricts oil flow
To maintain a constant pressure in the compressor
Controls the operation of the compressor and valves to maintain the set temperature

61

Stredne ťažká

What is the purpose of oil level regulators in a refrigeration system?


They control the pressure in the condenser
They control the evaporator temperature
Maintains the correct oil level in the compressor
They drain off excess refrigerant

62

Stredne ťažká

What is the function of the liquid receiver in relation to system tightness?


It controls the evaporating temperature by varying the circulating charge
It stores refrigerant; checking its liquid level helps detect charge loss
It regulates the oil returning to the compressor
It keeps the whole system at constant pressure regardless of load

63

Stredne ťažká

What is the role of a gauge manifold with thermometers (temperature probes)?


It relieves pressure if it is exceeded
It controls oil level
It measures pressures and temperatures to determine superheat and subcooling and thus assess the system charge (indirect leak check)
It monitors refrigerant moisture content

64

Stredne ťažká

What is the role of defrost controls?


They control compressor discharge pressure during defrost
They drain excess oil from the evaporator to the receiver
They protect the evaporator from icing and damage that could lead to leaks
They monitor the moisture content of the refrigerant

65

Stredne ťažká

Where can the lists of fluorinated greenhouse gases be found?


In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases
In a regulation of the Minister of Economy on the list of fluorinated greenhouse gases
In Annexes I–III to Regulation (EU) 2024/573 of the European Parliament and of the Council
In the Vienna Convention for the Protection of the Ozone Layer

66

Stredne ťažká

Where can the lists of ozone-depleting substances be found?


In a regulation of the Minister of the Environment on the list of controlled substances
In the Vienna Convention for the Protection of the Ozone Layer
In Annexes I and II to Regulation (EU) 2024/590 of the European Parliament and of the Council
In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases

67

Stredne ťažká

Why is ammonia (R717) classed as a toxic refrigerant?


Because it does not react with water, making neutralisation difficult
Because it is colourless and odourless and therefore hard to detect
It severely irritates the respiratory tract, eyes and skin, and is poisonous when inhaled at higher concentrations
Because it is heavier than air and displaces oxygen

68

Stredne ťažká

Where and by when must entities obliged under the Polish Act of 15 May 2015 submit annual reports on ODS and F-gases?


By 31 January, in the Central Register of Operators (CRO)
By the end of the calendar year, on a form at a regional office of the Office of Technical Inspection (UDT)
By 31 March, electronically to the Ministry of Climate and Environment
By 28 February of the following year, electronically via the Reports Database (BDS) run at the Institute of Industrial Chemistry (ICHP)

69

Stredne ťažká

Which installation measure has a major impact on compressor energy efficiency?


Proper evacuation and dehydration of the system (removing air and moisture)
Installing a suction line smaller than recommended
Charging extra refrigerant 'as a reserve' above the nameplate value
Omitting the filter-drier to reduce flow resistance

70

Stredne ťažká

How does regular oil-level monitoring affect compressor operation?


It ensures proper lubrication and limits wear and energy losses
It increases cooling capacity above nominal
It allows any type of oil to be topped up
It allows the crankcase heater to be omitted

71

Stredne ťažká

Regulation (EU) 2024/590 relates to:


Ozone-depleting substances
Alternative refrigerants replacing fluorinated greenhouse gases
Health and safety during refrigerant recovery
Conditions for F-gas certification of companies recovering and reclaiming refrigerants

72

Stredne ťažká

What is the significance of proper suction and discharge pressure control?


It keeps the compressor at optimal conditions (suction pressure as high and condensing pressure as low as permissible)
Pressures do not affect energy use
The highest possible condensing pressure is best
The lowest possible suction pressure is best

73

Stredne ťažká

Which maintenance measure reduces compressor energy consumption?


Replacing the filter-drier when the pressure drop or moisture indicator shows it is necessary
Raising the high-pressure switch setting
Permanently disabling the crankcase heater
Topping up refrigerant at every service visit

74

Stredne ťažká

How does air (non-condensable gas) in the system affect operation?


It improves condenser heat transfer
It only affects the sight-glass indication
It lowers the condensing pressure
It raises the condensing pressure and reduces efficiency

75

Stredne ťažká

What role do controls play in compressor efficiency?


They increase the circulating refrigerant charge
They matter only in NH₃ systems
They enable optimised operation and lower energy use (e.g. floating head pressure, capacity matching)
They provide safety only, with no energy effect

76

Stredne ťažká

How does suction superheat at the compressor affect efficiency?


Zero suction superheat is optimal
Superheat has no effect
The higher the superheat, the higher the efficiency
Excessive superheat reduces efficiency and raises the discharge temperature

77

Stredne ťažká

How does correct system layout affect efficiency?


It doesn't matter
It shortens pipe runs and limits pressure drops and energy losses
Longer pipes improve subcooling and always increase efficiency
It affects only appearance

78

Stredne ťažká

How important is suction pipe insulation?


It has no effect
It increases energy consumption
It limits heat gain and excessive superheat, improving efficiency
It is needed only for appearance

79

Stredne ťažká

Which measure most improves condenser energy efficiency?


Raising the condensing pressure set point
Reducing fan speed to the minimum
Regular cleaning of heat-exchange surfaces
Increasing the refrigerant charge

80

Stredne ťažká

Which refrigerants damage the ozone layer?


All natural refrigerants
All refrigerants containing fluorine and hydrogen in their molecules
All refrigerants containing carbon in their molecules
All refrigerants containing chlorine or bromine in their molecules

81

Stredne ťažká

How does correct condensing pressure control affect efficiency?


It always increases energy use
It keeps the lowest pressure that still ensures proper expansion-valve feed, reducing energy use
It is best to keep a constant high condensing pressure all year
It has no effect

82

Stredne ťažká

How does insulation of heating and DHW pipework affect the efficiency of a heat pump system?


It doesn't matter
It impairs cooling
It reduces energy losses and improves overall system efficiency
It increases pressure

83

Stredne ťažká

Which measure most improves the energy efficiency of an air-cooling evaporator?


Raising the condensing temperature by a few kelvin
Increasing the refrigerant charge above nominal
Restricting the airflow through the evaporator
Defrosting at the right time and keeping the fins clean

84

Stredne ťažká

What does a Certificate A2 for natural persons (Implementing Regulation (EU) 2024/2215) authorise?


All activities (leak checks, installation, repair, maintenance, servicing, decommissioning, recovery) involving F-gases and hydrocarbons in equipment containing less than 3 kg, or less than 6 kg in labelled hermetically sealed systems
Only leak checks that do not entail breaking into the refrigerant circuit
All activities involving equipment using CO₂ (R744)
Only recovery of F-gases from equipment containing less than 3 kg (or 6 kg in hermetically sealed systems)

85

Stredne ťažká

How does too low superheat setting on the TEV affect performance?


It increases operational safety
It reduces refrigerant flow
It may lead to improved efficiency, but it increases the risk of the compressor becoming flooded with liquid
It has no effect

86

Stredne ťažká

What is the scope of Regulation (EU) 2024/573?


Health and safety requirements for brazing and welding on refrigeration installations
Only requirements for periodic leak checks of refrigeration equipment
Limiting emissions, use and marketing of F-gases, HFC phase-down, certification and reporting
Design requirements and conformity assessment for pressure equipment

87

Stredne ťažká

What is the main design difference in hydrocarbon refrigeration systems?


No need for safety measures
The need to eliminate ignition sources and limit the charge because of the refrigerant's flammability
Lower energy efficiency
Higher operating pressures

88

Stredne ťažká

How do compressors used in hydrocarbon systems differ?


They must operate at higher pressures than HFC compressors
They need no lubrication
They must be approved by the manufacturer for the specific flammable refrigerant (e.g. electrical components that are not ignition sources, suitable oil)
There is no difference

89

Stredne ťažká

How can you tell that the system has been overcharged with refrigerant?


It cannot be checked, because the sight glass is not intended for this
The compressor runs at a lower load and the suction pressure drops
Under normal operating conditions the condensing pressure and subcooling rise markedly because excess liquid floods the condenser and reduces its active surface
Even under a very small heat load, frost forms on the suction line

90

Stredne ťažká

Before charging the unit with refrigerant, it is essential to…


…carry out a tightness test (and evacuate the system)
…fill in the unit's data sheet
…carry out a trial start-up
…check the compressor suction and discharge connections

91

Stredne ťažká

What information must appear on the label of equipment containing F-gases?


That it contains an F-gas, its designation, quantity in kg and t CO₂ eq, and GWP
The weight and capacity of the pipework and the colour code of the casing paint
The manufacturer's logo, the unit weight and year of manufacture from the rating plate
Only the trade name of the refrigerant and the unit's serial number

92

Stredne ťažká

Which set of information best reflects the content of the equipment records required by Regulation (EU) 2024/573?


The make and model of the unit
Only the date of installation and the installer's name
Operator details, equipment details, type and quantity of refrigerant, and information on servicing and repairs
The owner, installer and service technician of the unit

93

Stredne ťažká

Who is responsible for keeping the equipment records?


The person responsible for risk assessment.
The operator of the unit or system.
There is no such obligation.
The equipment maintenance technician.

94

Stredne ťažká

Where are oil traps installed on the suction line?


At the inlet to every component of the refrigeration system
Immediately before the compressor suction connection
At the bottom of vertical suction risers with upward flow
Before the safety valve on the suction side

95

Stredne ťažká

Which symptoms with the compressor running indicate a refrigerant leak (undercharge)?


Low suction pressure, high superheat and negligible subcooling
Sight glass full of liquid and rising oil level in the crankcase
Rising liquid level in the receiver and increasing subcooling
Rising condensing and suction pressures with no superheat

96

Stredne ťažká

Which components of a refrigeration system are potential leak points subject to leak checks?


Only suction-side components
Joints, valves (including stems), seals (including those on replaceable filters and driers), parts subject to vibration and connections to safety and measuring devices
Only high-pressure-side components
Hermetic compressors, liquid receivers and liquid separators

97

Stredne ťažká

What pressure is used for the pressure tightness test of an installation?


A pressure chosen by the technician based on experience
Always 30 bar
A pressure equal to the maximum pressure measured during operation
The pressure specified in EN 378-2 or by the manufacturer, not exceeding the maximum allowable pressure of the system (PS)

98

Stredne ťažká

At which points of the unit must the leak check be carried out?


At all points where there is a potential risk of refrigerant leakage
Only on compressor shut-off valves, solenoid valves and filters
Only at connections of measuring instruments
Only on discharge-side components

99

Stredne ťažká

When can a unit be considered tight after a pressure test?


When gas bubbles appear after immersion in water
When the pressure drop does not exceed 0.1 bar regardless of the test duration
When it has been checked with a fixed electronic detector
When the pressure remains constant during the test (allowing for temperature-related changes); any unexplained pressure drop requires the leak to be located

100

Stredne ťažká

Which legal act currently sets out the obligation to check stationary refrigeration equipment containing F-gases for leaks, and how often this must be done?


Commission Regulation (EC) No 1516/2007
Regulation (EU) 2024/573
Implementing Regulation (EU) 2024/2215
Regulation (EU) No 517/2014

101

Stredne ťažká

How should the pressure be increased during a pressure tightness test?


As quickly as possible
Gradually, in stages, checking for leaks at each level until the test pressure is reached
In one step, by fully opening the nitrogen cylinder valve
In any way

102

Stredne ťažká

What electronic equipment should be used for leak checking?


Only hot-cathode devices
Detectors suited to the refrigerant in the system, with appropriate sensitivity, checked periodically
Only devices with an 'ion pump' sensor
Only detectors with an infrared sensor

103

Stredne ťažká

What documentation should be checked before starting a leak check?


Only the installation invoice and the first start-up report
The operator's fixed-asset inventory ledger
Attendance sheets of the plant-room staff for the year
The equipment records – especially recurring problems and previous leaks

104

Stredne ťažká

What information must be recorded in the leak check report?


Only the number of leaks found and the date of the check
The method used, the time spent on site and the cost of repair
Date, number and location of leaks, how they were repaired, technician details and signature
The date, a general note about the leak and the operator's signature

105

Stredne ťažká

What pressure should be used for the pressure tightness test?


Always 10–12 bar
A pressure not exceeding the maximum allowable pressure of the system (PS)
Always 2–3 bar
Any pressure, at the technician's discretion

106

Stredne ťažká

What is the temperature glide of a refrigerant?


A property of single-component refrigerants, for which one saturation temperature corresponds to a given pressure
The temperature rise of the vapour in the compressor
The temperature drop of the refrigerant across the expansion valve
In zeotropic mixtures, the difference between the temperatures at the start and end of a phase change (boiling or condensation) at constant pressure

107

Stredne ťažká

In which equipment is a leakage detection system required?


Equipment with ≥ 500 t CO₂ eq of Annex I F-gases (or ≥ 100 kg of Annex II Section 1 gases)
Equipment with 50 t CO₂ eq or more of F-gases, regardless of equipment type
Equipment with 30 kg or more of F-gases, regardless of their GWP
Equipment with 5 t CO₂ eq or more of F-gases, regardless of equipment type

108

Stredne ťažká

What should you check before using a portable electronic leak detector?


That it suits the refrigerant and has been checked as the manufacturer requires
That it holds a valid UDT inspection certificate
That it has been zeroed close to the suspected leak point
That it has an infrared sensor, as only this type is permitted

109

Stredne ťažká

Which certificate types (A1, A2, B, C, D, E) authorise leak checks of equipment containing F-gases?


A1, A2 and E
All except D
Only A1 and A2
Only E

110

Stredne ťažká

Why is it advisable to subcool the liquid refrigerant?


To allow a condenser with a smaller heat-exchange surface to be used
To ensure that liquid free of vapour bubbles enters the expansion valve
To allow a smaller expansion valve to be used
To lower the evaporating temperature in the evaporator

111

Stredne ťažká

What must be done after repairing a leak in the refrigeration unit of a refrigerated trailer?


Issue the invoice and leave the leak check to the next periodic service
Update the equipment records and carry out a leak check (it may be done directly after repair)
Charge an alternative refrigerant, start up and measure the parameters
Visually inspect only the bolted and brazed joints near the repair

112

Stredne ťažká

Recovery of fluorinated greenhouse gases means:


The collection and storage of fluorinated greenhouse gases from containers, products and equipment during maintenance or servicing or prior to their disposal.
The reuse of fluorinated greenhouse gases following a basic purification process.
The final decommissioning and withdrawal from service or use of a product or piece of equipment containing fluorinated greenhouse gases.
The reprocessing of fluorinated greenhouse gases to achieve their specified standard properties.

113

Stredne ťažká

Who is authorised to recover refrigerant from stationary refrigeration equipment containing F-gases?


The administrator of the operator's account in the register
A natural person holding a certificate of the relevant type (A1; A2. or D within their charge limit)
The owner of the installation
The operator

114

Stredne ťažká

How must recovered refrigerants be stored?


In any pressure vessel that has some form of approval
In any used refrigerant cylinder, provided it is leak-tight
In a labelled recovery cylinder with a dual valve and a valid inspection
In a disposable (non-refillable) cylinder that held the same refrigerant

115

Stredne ťažká

When should the recovery of fluorinated greenhouse gases be carried out:


Before the final disposal of equipment and, where applicable, during its servicing and maintenance.
Before each leak test of the equipment.
Only prior to the final disposal of equipment.
Always during servicing and maintenance of equipment.

116

Stredne ťažká

What should be done if recovered refrigerant is contaminated (e.g. with acid, air or moisture)?


Pass it through a particle filter and reuse it
Clean the mixture yourself using a filter-drier
Hand it over to a specialised, authorised company for reclamation or destruction
Add a special contaminant neutraliser

117

Stredne ťažká

What should be done if different refrigerants have been mixed in a storage cylinder?


Add a special refrigerant to the mixture
Pass it through a filter-drier and reuse it
Separate the mixture into its components yourself
Hand the mixture over to an authorised company – as a rule for destruction

118

Stredne ťažká

How does push-pull refrigerant recovery work?


Nitrogen is injected into the system, pushing the refrigerant into the atmosphere
Refrigerant is drawn alternately from the suction and discharge sides of the compressor
The recovery unit draws vapour from the recovery cylinder and pushes it into the system; the pressure difference forces liquid refrigerant out of the system into the cylinder
The recovery unit draws vapour from the system and condenses it in the cylinder

119

Stredne ťažká

What are the options for managing waste refrigerant?


Recovery, disposal
Reclamation, recovery
Recycling, reclamation, destruction
Disposal, storage

120

Stredne ťažká

Which management option restores recovered refrigerant to a quality equivalent to virgin product, so that it can be used by any undertaking?


Recycling
Destruction
Storage
Reclamation

121

Stredne ťažká

The lower the evaporating temperature, …


…the lower the density of the suction vapour and the lower the refrigerant mass flow rate
…the greater the density of the suction vapour and the lower the refrigerant mass flow rate
…the greater the density of the suction vapour and the greater the refrigerant mass flow rate
…the lower the density of the suction vapour and the greater the cooling capacity of the compressor

122

Stredne ťažká

How must transportable pressure vessels (e.g. refrigerant cylinders) be marked?


With the manufacturer's logo and date of manufacture
Only with weight and capacity marks
The marking is optional
Among other things: the number of the design and testing standard, marks of the approving country and the inspection body, the date of the initial inspection, and the manufacturer's and operational marks

123

Stredne ťažká

The recovery of refrigerants does not require the use of:


An electronic leak detector.
A refrigerant recovery station.
Scales with a measurement range suitable for the size of the cylinder being filled.
Hoses with shut-off valves.

124

Stredne ťažká

What functions does the compressor perform in a refrigeration system?


The compressor draws in refrigerant vapour from the evaporator, compresses it, and then forces it into the condenser, raising the pressure to the required condensing pressure.
The compressor compresses ambient air and increases the pressure of the refrigerant.
The compressor creates a vacuum on the suction side of the system
The compressor condenses the refrigerant.

125

Stredne ťažká

What is compressor flooding (liquid slugging)?


Excess oil in the condenser
A large amount of liquid refrigerant in a flooded evaporator, which is a normal operating condition
Liquid refrigerant or oil entering the compression chamber
Flooding of the compressor by rainwater

126

Stredne ťažká

Within what range is the compressor motor speed typically controlled using a frequency inverter?


Approximately 30 to 75 Hz, corresponding to about 60–150% of nominal capacity (depending on the compressor manufacturer)
By a maximum of 10%
From approximately 10% to 90% of nominal capacity
Speed control does not change the cooling capacity

127

Stredne ťažká

Why is it essential to observe the correct phase sequence for scroll compressors and screw compressors?


Because the motor speed would decrease, and consequently the compressor’s capacity.
Because changing the phase sequence would reverse the direction of rotation of the compressor rotors, which could result in damage to the compressors.
Because this type of compressor has difficulty starting up if the phase sequence is changed.
Because these types of compressors are sensitive to voltage drops.

128

Stredne ťažká

What compression ratio should each stage of a two-stage vapour-compression system have (rule of thumb)?


Equal to 1
Greater than 10
Greater than 18
Less than approximately 8

129

Stredne ťažká

Why is a shaft seal necessary in open-type compressors?


To prevent air from entering and refrigerant from leaking out of the compressor
Only to prevent oil leakage
To ensure the bearing remains lubricated
To protect the crankshaft bearing

130

Stredne ťažká

How can you check whether the liquid refrigerant is sufficiently subcooled?


Check whether the whole evaporator surface is covered with an even layer of frost
Check whether the liquid distributor upstream of the evaporator feels warm
Check by touch whether the condenser outlet is noticeably colder than ambient
Compare the liquid-line temperature with the saturation temperature at the measured condensing pressure

131

Stredne ťažká

Why is the compressor crankcase heated?


To increase dissolution of refrigerant in the oil and improve its viscosity
To keep the lubricating oil liquid
To limit refrigerant migration into, and dissolution in, the oil during standstill
To dehydrate the oil

132

Stredne ťažká

What are compressor packs (racks)?


Units with two-stage compressors
Sets of compressors connected in any configuration
Several compressors connected in parallel on a common frame with common suction and discharge headers
Several air-cooled condensers

133

Stredne ťažká

What is the main advantage of multi-compressor packs?


Stepwise capacity matching to demand, plus redundancy
Low purchase cost and easy installation without special controls
A smaller refrigerant charge than a single-compressor system
No need for compressor controls and safety devices

134

Stredne ťažká

What is meant by the operating envelope (application range) of a compressor?


A range determined only by the evaporating temperature
The permissible range of evaporating and condensing temperatures (to, tk), or the corresponding pressures, within which the compressor may operate
The capacity, refrigerant type and dimensions of the compressor
A range determined by the evaporating temperature at a given ambient temperature

135

Stredne ťažká

What are the basic functions of oil in a compressor?


Increasing the cooling capacity of the refrigerant
Sealing leaks that develop in the installation
Absorbing moisture from the refrigerant
Lubricating bearings and sliding surfaces, removing heat, and sealing clearances (e.g. between piston and cylinder, or rotors)

136

Stredne ťažká

What are the most effective ways of controlling compressor cooling capacity?


Partially covering the evaporator
An expansion valve
Changing the displacement: varying the rotational speed or unloading cylinders
Pressure control valves

137

Stredne ťažká

What does hot-gas bypass capacity control involve?


Bypass is not used for capacity control
High-pressure liquid is injected into the suction to increase capacity
Part of the hot discharge gas is passed through a bypass valve to the suction side (or evaporator inlet), reducing the effective capacity
The compressor speed is varied

138

Stredne ťažká

What is the fundamental difference between hermetic and semi-hermetic compressors?


The semi-hermetic compressor has no motor inside the casing
Semi-hermetic compressors run more quietly as a complete unit
Both can be dismantled; they differ only in cooling capacity
The semi-hermetic casing is bolted (can be opened); the hermetic one is welded

139

Stredne ťažká

How does a scroll compressor work?


It is a positive-displacement compressor in which compression results from the interaction of a fixed and an orbiting scroll.
A scroll compressor is also known as a turbo compressor.
It uses two screws to compress the refrigerant.
It is a type of piston-type device.

140

Stredne ťažká

What physical process takes place in the evaporator?


The secondary fluid (glycol, water) evaporates while the refrigerant condenses
The refrigerant condenses
The refrigerant is subcooled as a liquid
The liquid refrigerant evaporates, absorbing heat, and the vapour is slightly superheated at the outlet

141

Stredne ťažká

What is the purpose of compressor capacity control?


To increase the condensing pressure
To ensure compressor lubrication
To match the cooling capacity to the current demand
To match capacity to the condensing temperature

142

Stredne ťažká

Why is inverter speed control advantageous for refrigeration compressors?


It enables continuous, smooth control of cooling capacity
It can be used with any compressor to ensure lubrication
Reducing the speed improves oil return to the compressor
It increases compressor capacity above nominal at any frequency

143

Stredne ťažká

Does the suction gas temperature affect the cooling capacity of the compressor?


Yes, but only in reciprocating compressors, not scroll
No – capacity depends only on the compressor displacement
Yes, but only if the suction gas is deeply cooled
Yes – higher temperature lowers vapour density, mass flow and capacity

144

Stredne ťažká

In the case of compressor units fitted with an oil level control system, is it necessary to install the compressors at the same height?


No.
Only scroll compressors.
Only screw compressors.
Yes.

145

Stredne ťažká

What functions does a compressor powered by the vehicle’s engine perform in a transport refrigeration system?


This compressor creates a vacuum on the suction side of the system whilst the vehicle’s engine is switched off.
The compressor compresses ambient air and increases the pressure of the refrigerant.
This compressor condenses the refrigerant whilst the vehicle is in motion.
This compressor draws in refrigerant vapour from the evaporator, compresses it and then forces it into the condenser whilst the vehicle’s engine is running.

146

Stredne ťažká

Which media most commonly absorb heat from the refrigerant in the condenser?


Air and CO₂
Only a water–glycol mixture
Air or water
Ammonia

147

Stredne ťažká

What is the function of the condenser in refrigeration systems?


Absorption of heat rejected in the regenerative heat exchanger
Releasing to the environment the heat absorbed in the evaporator and the heat added during compression
Releasing only the heat from the compressor into the surroundings
Releasing only the heat absorbed in the evaporator into the surroundings

148

Stredne ťažká

If the refrigerant temperature on the high-pressure side is above its critical temperature, condensation…


…always occurs regardless of temperature
…does not depend on temperature
…occurs provided a special condenser is used
…does not occur

149

Stredne ťažká

How is liquid subcooling usually achieved in a refrigeration system?


In the final section of the condenser (or in an additional subcooler)
By dissolving the refrigerant in oil
With an additional heat exchanger using liquid nitrogen
With hot high-pressure vapour

150

Stredne ťažká

What is the purpose of condenser fan speed control?


Only to protect against exceeding the maximum condensing pressure
To disperse refrigerant in the event of a leak
To keep the condensing pressure at the correct level
To reduce energy efficiency

151

Stredne ťažká

Which international agreement introduced the global phase-down of HFC production and consumption?


The Kigali Amendment to the Montreal Protocol
The Paris Agreement
The Vienna Convention for the Protection of the Ozone Layer
The Kyoto Protocol

152

Stredne ťažká

Which international treaty governs the phase-out of ozone-depleting substances (CFCs, HCFCs)?


The UN Framework Convention on Climate Change (UNFCCC)
The Montreal Protocol
The Stockholm Convention
The Paris Agreement

153

Stredne ťažká

Can HFC refrigerant recovered during a repair be put straight back into the same equipment without any cleaning (filtering/drying)?


Yes, if less than 24 hours have passed
Yes, if the operator agrees
Yes, always
No – recovered F-gas may be used for filling only after it has been recycled or reclaimed

154

Stredne ťažká

Who may purchase HFCs for servicing refrigeration equipment?


Only a person holding the relevant certificate or an undertaking employing such persons
Any adult
Only the equipment operator
Any business

155

Stredne ťažká

Under what condition may non-hermetically sealed split air conditioning charged with F-gas be sold to an end user?


When evidence is provided that installation will be carried out by a certified undertaking
Only if the unit contains less than 3 kg of refrigerant
Unconditionally
When the user signs a statement that they will install it themselves

156

Stredne ťažká

By when must the holder of an F-gas certificate issued under Regulation (EU) No 517/2014 first complete refresher training or an evaluation process?


By 31 December 2030
By 12 March 2025
Never – the certificate is valid indefinitely
By 12 March 2029 (and then at least every 7 years)

157

Stredne ťažká

What must the holder of a Category I certificate (Regulation 2015/2067) do to continue using it?


Update their knowledge to the level of Certificate E
Nothing – Category I automatically becomes A1
Apply for an extension without training
Update their knowledge and skills to the level of Certificate A1 (Annex I to Regulation 2024/2215)

158

Stredne ťažká

What does Certificate C under Implementing Regulation (EU) 2024/2215 authorise?


Recovery of F-gases from equipment <3 kg
All activities in Article 2(1) in relation to ammonia (NH₃)
All activities in relation to CO₂
Leak checks without breaking into the circuit

159

Stredne ťažká

May a person enrolled in a certification training course carry out certified activities?


No, never
Yes – with no time limit, if employed by a certified company
Yes – independently, for 6 months
Yes – under the supervision of a certified person, for no more than 24 months in total

160

Stredne ťažká

How long must the operator keep the records of equipment subject to leak checks, if they are not kept in a national database?


At least 5 years
At least 2 years
Until the equipment is decommissioned
At least 1 year

161

Stredne ťažká

What distinguishes class 2L refrigerants from class 2?


A maximum burning velocity of no more than 10 cm/s
Higher toxicity
No lower flammability limit
Heat of combustion above 19 MJ/kg

162

Stredne ťažká

What is the lower flammability limit (LFL) of propane R290?


Approx. 0.038 kg/m³ (approx. 2.1% by volume)
Approx. 0.307 kg/m³
Approx. 0.38 kg/m³
Approx. 1.8 kg/m³

163

Stredne ťažká

Equipment marked 'Ex II 3G' may be used in zone:


20 (dusts)
0
1
2 (explosive gas atmosphere unlikely and short-lived)

164

Stredne ťažká

How is explosion hazard zone 2 defined?


An explosive atmosphere is not likely in normal operation and, if it occurs, persists only for a short period
An explosive atmosphere is present continuously or for long periods
An explosive atmosphere is likely to occur in normal operation
An area where flammable refrigerants are never used

165

Stredne ťažká

Under which UN number is propane (R290) carried under ADR?


UN 1005
UN 1978
UN 3337
UN 3252

166

Stredne ťažká

At what concentration should a portable flammable gas detector used for R290 work raise an alarm at the latest?


At 5% propane by volume
No higher than 25% of LFL
At 150% of LFL
At 100% of LFL

167

Stredne ťažká

How should a recovery cylinder be prepared before filling it with a hydrocarbon refrigerant?


Evacuate it (no air) and label it for the specific flammable refrigerant
Purge it with compressed air
No preparation is needed
Partly fill it with nitrogen to 5 bar

168

Stredne ťažká

What is the correct approach in a risk analysis before work on an HC system?


First select PPE, then possibly remove ignition sources
First eliminate hazard sources (e.g. ignition sources); where this is not possible, identify them and apply mitigating measures (ventilation, detection, PPE)
Having a fire extinguisher is sufficient
The risk analysis is done after the work is finished

169

Stredne ťažká

Which property of ammonia helps people detect a leak early?


It is odourless
It is denser than air
It is yellow in air
A very low odour threshold (a few ppm)

170

Stredne ťažká

What hazard does a large CO₂ leak in an enclosed room pose to people?


CO₂ is completely safe
Formation of hydrogen fluoride
Accumulation near the floor and asphyxiating/toxic effects at high concentrations
Explosion of the mixture with air

171

Stredne ťažká

What is floating head pressure and what does it achieve?


It increases subcooling by flooding the condenser
It keeps a constant high condensing pressure all year
It lets the condensing pressure fall with ambient temperature, reducing compressor work and raising COP (requires an expansion valve that works at a small pressure difference)
It means switching condenser fans off periodically

172

Stredne ťažká

How do SEER/SCOP differ from EER/COP?


SEER/SCOP are seasonal indicators accounting for part load and climate (EN 14825); EER/COP refer to a single operating point (EN 14511)
EER/COP are always higher than SEER/SCOP
There is no difference – they are synonyms
SEER/SCOP apply only to natural-refrigerant equipment

173

Stredne ťažká

Which design approach can significantly reduce the F-gas charge of a large refrigeration installation?


Larger liquid-line diameters
An indirect (secondary-coolant) system or a cascade with a natural refrigerant in the low stage, plus heat exchangers with small internal volume
Adding a second liquid receiver
Omitting pipe insulation

174

Stredne ťažká

Why must the charge of small, critically charged R290 systems be weighed to within a few grams during service?


Because scales are not needed – charging is done by sight glass
Small charge deviations significantly change superheat/subcooling and efficiency, and overcharge increases the risk in a leak
Because extra R290 improves efficiency
Because R290 is more expensive than HFCs

175

Stredne ťažká

Which information must be entered in the equipment records after a leak check?


The date and result of the check and the identity of the undertaking and person who performed it (with certificate number)
Only the operator's signature
Only the equipment's energy consumption
Only the date of the check

176

Stredne ťažká

What must be done when an indirect method (e.g. parameter analysis) indicates a possible leak?


Nothing – indirect methods are sufficient
Record it and check at the next periodic inspection
Top up the refrigerant and end the check
Carry out a direct-method examination to locate the leak