What is the base unit of mass in the International System of Units (SI)?


N
kg
t
lb (pound)

2

Medium

What process takes place in the condenser of a refrigeration system?


The refrigerant absorbs heat from the surroundings and evaporates
The refrigerant rejects only the heat generated in the compressor
Hot vapour discharged by the compressor is desuperheated, condensed, and the resulting liquid is slightly subcooled
The secondary fluid (glycol, water) condenses while the refrigerant evaporates

3

Medium

What mainly determines the condensing temperature of an air-cooled condenser?


The compressor discharge temperature
The evaporating temperature
The superheat
The ambient (inlet) air temperature

4

Medium

Why does heat flow from the condenser to the surroundings?


Because the compressor pushes heat directly into the surroundings
Because HFC refrigerants attract heat from the surroundings
Because the pressure in the condenser is lower than ambient
Because the condensing temperature is higher than the ambient temperature, and heat flows spontaneously from a warmer to a colder body (second law of thermodynamics)

5

Medium

What should you mainly pay attention to when operating a condenser?


That the outlet air temperature is higher than the condensing temperature
That the inlet air temperature is lower than the outlet air temperature
The colour of the condenser casing
Its general condition and the cleanliness of the heat-exchange surfaces

6

Medium

What criteria should be considered when selecting a suitable condenser?


The required capacity of the condenser and the technical specifications declared by the manufacturer
Only the size and number of fans
Fan noise, connection diameters and colour
Only own experience and the dimensions

7

Medium

How do contaminants (dust, particulates, deposits) affect the performance and efficiency of heat exchange surfaces in condensers?


Contaminants do not significantly affect the efficiency and effectiveness of the heat exchange surfaces in condensers.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause a reduction in condensing pressure.
Contaminants increase the heat transfer area and reduce the condensing pressure.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause an increase in condensing temperature and pressure, which in turn leads to a reduction in the condenser’s efficiency.

8

Medium

How does the capacity of an air-cooled condenser change when it becomes dirty?


It increases because the fan speed rises
It increases
It remains unchanged
It decreases

9

Medium

What is the main consequence of heavy frost on an air-cooling evaporator?


A rise in evaporating pressure
Reduced heat transfer and airflow, resulting in a drop in cooling capacity and evaporating temperature
A rise in the cooled-air temperature with no effect on capacity
An increase in condenser subcooling

10

Medium

What happens when the evaporation temperature drops?


The discharge temperature decreases.
The condenser fan speed increases.
The compressor’s cooling capacity increases.
The compressor’s cooling capacity decreases.

11

Medium

When is natural (off-cycle, air) defrosting possible?


Only in freezer rooms below −18 °C
Only in coolers fitted with speed-controlled fans
When the air passing through the cooler is above 0 °C
Never – electric heaters must be used in every air cooler

12

Medium

When does frost form on the surface of an air-cooling evaporator?


Only when the system runs continuously
Always, in every air cooler
When the evaporator surface temperature is below 0 °C and below the dew point of the air
Only when the room air temperature falls below 0 °C

13

Medium

In extensive pipework systems, flash gas (secondary evaporation) in the liquid line can be prevented by…


…increasing the length of the liquid line
…additional subcooling of the liquid
…using smaller-diameter pipes
…insulating the discharge line between the compressor and the condenser

14

Medium

How does hot gas defrosting of the evaporator work?


This involves reversing the direction of rotation of the compressor.
Heated vapour (hot gas) from the compressor is directed into the evaporator piping.
We swap the outlet and inlet sides of the evaporator.
We switch on the gas heater directed at the evaporator.

15

Medium

What is the function of the evaporator in a refrigeration system?


It transfers heat from the medium being cooled to the boiling refrigerant.
It evaporates the water flowing through the evaporator.
It ensures that the refrigerant is superheated over the largest possible heat exchange surface area.
It cools the refrigerant.

16

Medium

What condition must electric heaters for evaporator defrosting meet?


They must be located beneath the evaporator
They must have good thermal contact with the heat-exchange surface (e.g. inserted in the fin block)
They must be in direct contact with the refrigerant
Heat from the heaters must be carried by the running fans

17

Medium

Refrigerant distributor:


ensures an even distribution of the refrigerant to the individual sections of the evaporator.
ensures even distribution of the refrigerant to the individual sections of the condenser.
acts as a buffer for the refrigerant in the event that the pressure upstream of the expansion valve is exceeded.
ensures the even distribution of the refrigerant discharged by compressors connected in parallel.

18

Medium

What defrosting methods are used for air coolers?


Electric, hot gas, water spray and natural (at positive temperatures)
Only by switching off the fans with the compressor running
Electric only – other methods are not permitted in refrigeration
Natural only – other methods are ineffective and uneconomic

19

Medium

The boiling point of a liquid rises when the pressure above the liquid…


…rises
…remains constant
…varies depending on the ambient temperature
…falls

20

Medium

MOP in thermostatic expansion valves stands for:


self-cleaning of the valve in the event of moisture in the refrigerant freezing.
maximum operating pressure.
maximum pressure switch protection.
minimum flow opening.

21

Medium

The function of a thermostatic expansion valve (TEV) is:


to meter refrigerant into the evaporator according to the superheat of the vapour leaving the evaporator
to maintain a constant condensing pressure
to maintain a constant compressor suction pressure
to adjust the evaporating pressure in the condenser

22

Medium

What type of compressor motor can be used with a capillary tube?


An electronically commutated motor
A low-speed motor
A low-starting-torque motor (pressures equalise during standstill)
A high-starting-torque motor must be used

23

Medium

What does a thermostatic expansion valve control?


The condensing pressure
The discharge temperature
The mass flow of refrigerant fed into the evaporator
The temperature in the cold room

24

Easy

The refrigerant absorbs heat when…


…it freezes
…it is subcooled
…it condenses
…it evaporates

25

Medium

What does the manufacturer state as the factory setting of a thermostatic expansion valve?


the static superheat of the valve.
the degree of refrigerant expansion.
the superheat value during valve operation.
the degree to which the valve is filled with refrigerant liquid.

26

Medium

Where is a new or repaired system with an expansion valve and liquid receiver charged?


Through the capillary tube outlet during normal system operation
In the liquid phase on the high-pressure side, with the compressor stopped
Anywhere – the charging point does not matter
In the liquid phase into the compressor suction, with the compressor running

27

Medium

What does a thermostatic or electronic expansion valve control?


The compressor speed
Subcooling, by adjusting condensing pressure
The amount of refrigerant fed to the evaporator according to superheat
The evaporating pressure – closing below the set point

28

Medium

What does the MOP function of thermostatic expansion valves mean?


The valve maintains a constant condensing pressure
The valve limits subcooling
The valve limits the maximum evaporating (suction) pressure, protecting the compressor motor from overload, e.g. after defrost
The valve prevents motor overheating by injecting liquid into the compressor

29

Medium

The lower the liquid temperature upstream of the expansion valve, (at the same mass flow)…


…the lower qo and the lower energy efficiency
…the lower qo, with Qo unchanged
…the higher the specific refrigerating effect qo [kJ/kg] and the higher the cooling capacity Qo
…the lower qo and the lower Qo

30

Medium

How should the MOP point of an expansion valve be selected relative to the highest normal evaporating temperature?


About 7 K lower than that temperature
Higher by approx. 20 K
A few kelvin higher (approximately 7 K)
Freely – the MOP value is irrelevant

31

Medium

What is the function of the suction pressure regulator?


It limits the suction pressure and protects the compressor from excessively high suction pressure.
It prevents a drop in suction pressure and, if necessary, shuts down the refrigeration system.
To maintain the suction pressure at the highest possible level.
It maintains the evaporation pressure at a constant level.

32

Medium

What is the function of the valve regulating water flow through the condenser?


To maintain the condensing pressure at the highest possible level.
To maintain the condensing pressure at a constant level.
To maintain the condensing pressure at the lowest possible level.
To maintain the water temperature at the highest level.

33

Medium

The use of a refrigerant distributor requires a thermostatic expansion valve ...


... with external pressure equalisation.
... with an adsorption-type sensor filling.
... with internal pressure equalisation.
... with a MOP function.

34

Medium

What properties should good insulation materials have?


Low thermal conductivity (and low water absorption, vapour tightness)
High thermal conductivity
The ability to absorb large amounts of moisture
An antistatic coating

35

Medium

When is refrigerant vapour superheated?


When the evaporating temperature is lower than the ambient temperature
When the compressor motor temperature rises excessively
When its temperature is higher than the saturation temperature corresponding to its pressure
When the pressure on the discharge side is higher than on the suction side

36

Medium

How can you check whether the liquid refrigerant is reaching the expansion valve without vapour bubbles?


We check using a liquid pressure gauge.
We check using a pressure gauge fitted on the discharge side of the compressor.
We check this using a sight glass.
We are unable to check this.

37

Medium

Where does the liquid line run?


Between the evaporator and the suction-line heat exchanger
From the condenser (liquid receiver) to the expansion valve
Between the evaporator and the compressor
Between the compressor and the condenser

38

Medium

What is the function of the liquid receiver in a refrigeration system?


To act as a reserve when the required charge is unknown
To further subcool the condensed refrigerant
To store refrigerant and compensate for changes in the circulating charge as the heat load varies
To collect liquid refrigerant and excess oil

39

Medium

What is the purpose of the liquid receiver during service work?


It allows pump-down and temporary storage of the refrigerant
It is a reserve when the installer does not know the required charge
It collects excess oil circulating in the system
It further subcools the refrigerant before the expansion valve

40

Medium

Where should the liquid receiver be installed?


It should be fitted after the evaporator.
It should be fitted just before the compressor.
It should be installed downstream of the condenser, upstream of the expansion valve.
It should be fitted between the compressor and the condenser.

41

Medium

What is the function of the suction pressure regulator fitted to the suction pipe when the compressor starts up?


It regulates the condensing pressure.
It closes when the suction pressure upstream of the compressor drops.
It opens when the suction pressure upstream of the compressor drops.
It regulates the evaporation pressure.

42

Medium

The use of microchannel heat exchangers, compared with conventional heat exchangers made of copper tubes and fins, results in:


A reduction in the system’s energy efficiency.
A reduction in refrigerant charge and, typically, higher energy efficiency.
An increase in the amount of refrigerant in the system and an increase in condensing pressure.
There is no effect whatsoever on either the amount of refrigerant or energy efficiency.

43

Medium

Which refrigerants belong to the HFC group?


R134a, R404A, R507A, R410A.
R134a, R32, R22, R507A, R290.
R22, R401A.
R11, R12, R502.

44

Medium

Which refrigerants belong to the HFO group?


R134a, R290.
R134a, R404A.
R1234yf, R1234ze(E).
R22, R12.

45

Medium

What are the characteristics of R410A refrigerant compared to R407C refrigerant?


The saturation pressure of R407C is 150% higher than that of R410A.
The saturation pressure of both refrigerants is roughly the same.
The saturation pressure of R407C refrigerant is much higher than that of R410A.
The saturation pressure of R410A refrigerant is higher than that of R407C.

46

Medium

What does the TEWI indicator define?


The ability of the ozone layer to recover
The global warming potential of a gas relative to CO₂ over a 100-year horizon
Total Equivalent Warming Impact: the sum of direct emissions (leakage and refrigerant losses at disposal) and indirect emissions (CO₂ from generating the energy consumed by the equipment) over its lifetime
The impact of a refrigerant on the ozone layer

47

Medium

What are the characteristics of R452A compared with R404A?


The temperature glide of R452A is half that of R404A
It is a non-flammable (A1) HFC/HFO blend with properties similar to R404A and a GWP about 45% lower
Both are azeotropic and have no temperature glide
It is a flammable and toxic single-component HFC

48

Medium

What distinguishes R1234yf from R134a?


A higher normal boiling point
A higher critical temperature
Higher toxicity
It is mildly flammable (class A2L), whereas R134a is non-flammable (A1)

49

Medium

How does CO₂ (R744) compare with R134a?


Its temperature glide is 7 K greater than that of R134a
It has a lower critical temperature, much higher operating pressures and a much higher volumetric cooling capacity (smaller compressors and pipes)
Unlike R134a, it is an azeotropic mixture
It has identical properties and is a drop-in replacement for R134a

50

Medium

Which of the following is NOT a fluorinated greenhouse gas?


Hydrofluorocarbons (HFCs).
Sulphur hexafluoride (SF6).
Perfluorocarbons (PFCs).
Carbon dioxide (CO₂).

51

Medium

What is the greenhouse effect?


Chlorine compounds destroy stratospheric ozone, increasing UV radiation at the surface
Dust in the atmosphere reflects sunlight, lowering the average surface temperature
Greenhouse gases absorb and re-emit the Earth's infrared radiation, warming the lower atmosphere
Clouds reflect ultraviolet radiation, which makes the air near the surface warmer

52

Easy

What does the GWP indicator mean?


The annual rise in mean air temperature caused by the emission of 1 kg of the gas
The ability of a substance to restore the ozone layer
Global Warming Potential: the climate warming impact of 1 kg of a gas compared with 1 kg of CO₂ (GWP = 1) over a defined time horizon, usually 100 years
Ozone depletion potential

53

Medium

How do refrigeration systems contribute to the greenhouse effect?


Indirectly (through energy consumption) and directly (through emissions of refrigerant into the atmosphere)
Through oil emitted into the atmosphere from the condenser and filter
Only through the heat rejected by the condenser
Only through CO₂ given off by the compressor motor

54

Medium

What is the greenhouse effect?


The filtering of solar radiation by the atmosphere
The formation of a layer that traps only heat from fuel combustion in aircraft
The trapping of heat in the Earth's atmosphere, which hinders the radiation of heat into space
The absorption of solar radiation by the Earth's surface

55

Medium

Which EU regulation is currently the primary piece of legislation governing the use of fluorinated greenhouse gases (F-gases) in the European Union?


Regulation (EU) 2015/1188
Regulation (EU) 2024/573
Directive 2009/125/EC
Regulation (EU) No 517/2014

56

Medium

What is the main objective of Regulation (EU) 2024/573?


Prevention of F-gas emissions and the achievement of the EU’s climate targets
Standardising metal recycling standards
To facilitate the import of electrical appliances
To reduce taxes on refrigeration equipment

57

Medium

What are the ecodesign obligations of manufacturers of refrigerating appliances?


Only declaring F-gas quantities under Regulation (EU) No 517/2014
Meeting implementing regulations (e.g. 2019/2019, 2015/1095): efficiency, spare parts, reparability
Only using energy labels under Regulation (EU) 2024/573
Only implementing an ISO 9001 quality management system

58

Medium

What is the main objective of EU ecodesign legislation (Directive 2009/125/EC, now Regulation (EU) 2024/1781 – ESPR)?


To increase sales of electrical appliances in the EU
To facilitate imports from outside the EU
To reduce the negative environmental impact of products by improving energy efficiency, durability and recyclability
To standardise the appearance of products in the EU

59

Medium

What is the function of a ball valve in a refrigeration system?


Enables the refrigerant flow to be completely shut off
It prevents excessive pressure build-up in the system
It measures the moisture content of the refrigerant
It regulates the temperature of the refrigerant

60

Easy

What is the main function of a safety valve?


It monitors the moisture content of the refrigerant
Discharges refrigerant when the set pressure is exceeded
Prevents the evaporator from freezing
It controls the oil level in the compressor

61

Medium

How do certain gases contribute to the greenhouse effect?


They deplete the ozone layer, so more solar radiation reaches the surface
They trap thermal radiation that the Earth would otherwise emit into space
They limit UV radiation reaching the Earth's surface, changing the heat balance
They heat the air through chemical reactions with atmospheric oxygen and nitrogen

62

Medium

What is the purpose of a sight glass (with moisture indicator)?


Emergency shut-off of flow
Measuring condenser temperature
Visual assessment of the refrigerant condition in the liquid line (bubbles) and of system moisture
Regulating compressor pressure

63

Medium

What is the function of the temperature regulator in a refrigeration system?


It restricts oil flow
It drains excess refrigerant into the receiver
Controls the operation of the compressor and valves to maintain the set temperature
To maintain a constant pressure in the compressor

64

Difficult

What is the role of a suction liquid separator (also in systems with flammable or toxic refrigerants)?


It is used only to measure moisture
It heats the refrigerant before the evaporator
It prevents liquid refrigerant from entering the compressor
It separates liquid from oil

65

Difficult

What is the function of an oil separator in systems using flammable or toxic refrigerants?


Separates oil from the refrigerant and facilitates the return of oil to the compressor
It prevents liquid from entering the compressor
Heats the refrigerant before it enters the evaporator
They are used solely to measure the moisture content of the refrigerant

66

Medium

What is the purpose of oil level regulators in a refrigeration system?


They control the evaporator temperature
They control the pressure in the condenser
They drain off excess refrigerant
Maintains the correct oil level in the compressor

67

Medium

What is the function of the liquid receiver in relation to system tightness?


It controls the evaporating temperature by varying the circulating charge
It stores refrigerant; checking its liquid level helps detect charge loss
It regulates the oil returning to the compressor
It keeps the whole system at constant pressure regardless of load

68

Medium

What is the role of a gauge manifold with thermometers (temperature probes)?


It measures pressures and temperatures to determine superheat and subcooling and thus assess the system charge (indirect leak check)
It relieves pressure if it is exceeded
It monitors refrigerant moisture content
It controls oil level

69

Medium

What is the role of defrost controls?


They control compressor discharge pressure during defrost
They drain excess oil from the evaporator to the receiver
They protect the evaporator from icing and damage that could lead to leaks
They monitor the moisture content of the refrigerant

70

Easy

What is the unit of pressure in the International System of Units (SI)?


Pa (pascal)
atm (standard atmosphere)
bar (gauge)
psi (pound per square inch)

71

Medium

Where can the lists of fluorinated greenhouse gases be found?


In the Vienna Convention for the Protection of the Ozone Layer
In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases
In Annexes I–III to Regulation (EU) 2024/573 of the European Parliament and of the Council
In a regulation of the Minister of Economy on the list of fluorinated greenhouse gases

72

Medium

Where can the lists of ozone-depleting substances be found?


In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases
In a regulation of the Minister of the Environment on the list of controlled substances
In Annexes I and II to Regulation (EU) 2024/590 of the European Parliament and of the Council
In the Vienna Convention for the Protection of the Ozone Layer

73

Difficult

Why are PFAS formed by the decomposition of certain F-gases (e.g. TFA from HFOs) problematic?


They are very persistent, accumulate in the environment (e.g. water) and may be toxic
They cause rapid cooling of the atmosphere
They are readily biodegradable
They are climate- and environment-neutral

74

Medium

Where and by when must entities obliged under the Polish Act of 15 May 2015 submit annual reports on ODS and F-gases?


By the end of the calendar year, on a form at a regional office of the Office of Technical Inspection (UDT)
By 31 March, electronically to the Ministry of Climate and Environment
By 31 January, in the Central Register of Operators (CRO)
By 28 February of the following year, electronically via the Reports Database (BDS) run at the Institute of Industrial Chemistry (ICHP)

75

Medium

Which installation measure has a major impact on compressor energy efficiency?


Omitting the filter-drier to reduce flow resistance
Proper evacuation and dehydration of the system (removing air and moisture)
Charging extra refrigerant 'as a reserve' above the nameplate value
Installing a suction line smaller than recommended

76

Medium

How does regular oil-level monitoring affect compressor operation?


It increases cooling capacity above nominal
It ensures proper lubrication and limits wear and energy losses
It allows any type of oil to be topped up
It allows the crankcase heater to be omitted

77

Easy

How do system leaks affect compressor energy efficiency?


They improve efficiency because condensing pressure drops
They affect only safety, not energy use
No effect as long as the system still cools
Refrigerant loss reduces capacity and increases energy use (longer run times, higher superheat)

78

Medium

Regulation (EU) 2024/590 relates to:


Health and safety during refrigerant recovery
Ozone-depleting substances
Conditions for F-gas certification of companies recovering and reclaiming refrigerants
Alternative refrigerants replacing fluorinated greenhouse gases

79

Medium

What is the significance of proper suction and discharge pressure control?


Pressures do not affect energy use
The lowest possible suction pressure is best
The highest possible condensing pressure is best
It keeps the compressor at optimal conditions (suction pressure as high and condensing pressure as low as permissible)

80

Medium

Which maintenance measure reduces compressor energy consumption?


Topping up refrigerant at every service visit
Permanently disabling the crankcase heater
Raising the high-pressure switch setting
Replacing the filter-drier when the pressure drop or moisture indicator shows it is necessary

81

Medium

How does air (non-condensable gas) in the system affect operation?


It improves condenser heat transfer
It raises the condensing pressure and reduces efficiency
It only affects the sight-glass indication
It lowers the condensing pressure

82

Medium

What role do controls play in compressor efficiency?


They provide safety only, with no energy effect
They matter only in NH₃ systems
They increase the circulating refrigerant charge
They enable optimised operation and lower energy use (e.g. floating head pressure, capacity matching)

83

Medium

How does suction superheat at the compressor affect efficiency?


Excessive superheat reduces efficiency and raises the discharge temperature
The higher the superheat, the higher the efficiency
Superheat has no effect
Zero suction superheat is optimal

84

Medium

How does correct system layout affect efficiency?


It doesn't matter
Longer pipes improve subcooling and always increase efficiency
It affects only appearance
It shortens pipe runs and limits pressure drops and energy losses

85

Medium

How important is suction pipe insulation?


It has no effect
It is needed only for appearance
It increases energy consumption
It limits heat gain and excessive superheat, improving efficiency

86

Medium

Which measure most improves condenser energy efficiency?


Raising the condensing pressure set point
Increasing the refrigerant charge
Regular cleaning of heat-exchange surfaces
Reducing fan speed to the minimum

87

Easy

How does a dirty condenser affect the operation of the refrigeration system?


Causes an increase in pressure and energy consumption by the compressor
It improves efficiency
It lowers the condensing pressure
It has no effect

88

Easy

Why is adequate airflow through an air-cooled condenser important?


It affects only noise
It doesn't matter
The lower the airflow, the lower the condensing pressure
It ensures effective heat rejection and low condensing pressure

89

Medium

Which refrigerants damage the ozone layer?


All refrigerants containing carbon in their molecules
All natural refrigerants
All refrigerants containing chlorine or bromine in their molecules
All refrigerants containing fluorine and hydrogen in their molecules

90

Easy

How does the presence of limescale in a water-cooled condenser affect performance?


It lowers the condensation temperature
Impairs heat exchange and increases energy consumption
It improves heat transfer
It has no effect

91

Medium

How does correct condensing pressure control affect efficiency?


It has no effect
It keeps the lowest pressure that still ensures proper expansion-valve feed, reducing energy use
It is best to keep a constant high condensing pressure all year
It always increases energy use

92

Easy

How do condenser leaks affect energy efficiency?


They lower the temperature
They improve efficiency
Causes refrigerant loss and a drop in efficiency
Have no effect

93

Easy

How important is the correct positioning of an air-cooled condenser?


It doesn’t matter
It should be close to heat sources
It should be installed in a well-ventilated area with unobstructed airflow
It should be housed in a small room

94

Easy

How does hot air recirculation affect the condenser?


It has no effect
It reduces the pressure
Impairs cooling and increases energy consumption
It improves efficiency

95

Medium

How does insulation of heating and DHW pipework affect the efficiency of a heat pump system?


It doesn't matter
It increases pressure
It impairs cooling
It reduces energy losses and improves overall system efficiency

96

Medium

Which measure most improves the energy efficiency of an air-cooling evaporator?


Raising the condensing temperature by a few kelvin
Restricting the airflow through the evaporator
Defrosting at the right time and keeping the fins clean
Increasing the refrigerant charge above nominal

97

Easy

How does evaporator icing affect the system’s operation?


It improves cooling performance
Impairs heat exchange and increases energy consumption
It lowers the condensation temperature
It has no effect

98

Easy

How does dirt on the evaporator surface affect its performance?


Impairs heat exchange and increases energy consumption
It reduces the pressure
It has no effect
It improves efficiency

99

Easy

What maintenance task is crucial for the evaporator?


Lack of maintenance
Reduced airflow
Regular cleaning and defrosting
Increasing the refrigerant charge

100

Medium

What does a Certificate A2 for natural persons (Implementing Regulation (EU) 2024/2215) authorise?


Only recovery of F-gases from equipment containing less than 3 kg (or 6 kg in hermetically sealed systems)
All activities (leak checks, installation, repair, maintenance, servicing, decommissioning, recovery) involving F-gases and hydrocarbons in equipment containing less than 3 kg, or less than 6 kg in labelled hermetically sealed systems
All activities involving equipment using CO₂ (R744)
Only leak checks that do not entail breaking into the refrigerant circuit

101

Easy

How does superheat at the evaporator outlet affect efficiency?


It only causes a temperature drop
It always improves performance
Excessive superheat reduces energy efficiency
It has no effect

102

Easy

How do leaks in the evaporator affect efficiency?


Have no effect
Increase capacity
These cause refrigerant loss and a drop in efficiency
Improves performance

103

Easy

How important is correct expansion valve adjustment?


It increases energy consumption
It doesn’t matter
Causes leaks
Ensures optimal evaporator charge and improves efficiency

104

Easy

How does inadequate insulation of suction (or secondary-coolant) pipes affect evaporator performance?


It has no effect
It improves efficiency
It causes cooling losses and increased energy use
It lowers the condensing temperature

105

Easy

How does correct TEV adjustment affect system energy efficiency?


It causes leaks
It has no effect
It increases energy use
It ensures optimal superheat and improves efficiency

106

Easy

What happens if the superheat set by the TEV is too high?


Efficiency will drop because the evaporator is not being fully utilised
Cooling efficiency will improve
The refrigerant charge will increase
It has no effect

107

Medium

How does too low superheat setting on the TEV affect performance?


It reduces refrigerant flow
It has no effect
It increases operational safety
It may lead to improved efficiency, but it increases the risk of the compressor becoming flooded with liquid

108

Easy

How do contaminants in the system affect the operation of the TEV?


Have no effect
They improve its performance
They lower the temperature
They can cause it to become blocked and reduce efficiency

109

Easy

What role does the filter-drier play in terms of system efficiency?


Removes moisture and contaminants, improving the system’s efficiency
It increases the amount of refrigerant
It doesn’t matter
It lowers the temperature

110

Easy

How does proper insulation of components (e.g. pipes near the TEV) affect the system?


It increases energy consumption
Prevents unwanted heat gains and improves efficiency
It doesn’t matter
It causes leaks

111

Medium

What is the scope of Regulation (EU) 2024/573?


Design requirements and conformity assessment for pressure equipment
Only requirements for periodic leak checks of refrigeration equipment
Limiting emissions, use and marketing of F-gases, HFC phase-down, certification and reporting
Health and safety requirements for brazing and welding on refrigeration installations

112

Easy

How important is it to check the operation of the condensing pressure control valve in the system?


It causes a significant rise in temperature
It has no effect
It increases energy consumption
Ensures operation within the optimum pressure range and reduces energy losses

113

Easy

How does the correct selection of a TEV affect energy efficiency?


It increases the amount of refrigerant
Ensures the system is matched to its capacity and operates optimally
It doesn’t matter
It lowers the temperature

114

Medium

How can you tell that the system has been overcharged with refrigerant?


Under normal operating conditions the condensing pressure and subcooling rise markedly because excess liquid floods the condenser and reduces its active surface
Even under a very small heat load, frost forms on the suction line
It cannot be checked, because the sight glass is not intended for this
The compressor runs at a lower load and the suction pressure drops

115

Medium

Before charging the unit with refrigerant, it is essential to…


…carry out a tightness test (and evacuate the system)
…carry out a trial start-up
…fill in the unit's data sheet
…check the compressor suction and discharge connections

116

Medium

What information must appear on the label of equipment containing F-gases?


The weight and capacity of the pipework and the colour code of the casing paint
The manufacturer's logo, the unit weight and year of manufacture from the rating plate
That it contains an F-gas, its designation, quantity in kg and t CO₂ eq, and GWP
Only the trade name of the refrigerant and the unit's serial number

117

Easy

What is the base unit of temperature according to the International System of Units (Système International d’Unités)?


K
°R
°F
°C

118

Medium

Which set of information best reflects the content of the equipment records required by Regulation (EU) 2024/573?


Operator details, equipment details, type and quantity of refrigerant, and information on servicing and repairs
Only the date of installation and the installer's name
The owner, installer and service technician of the unit
The make and model of the unit

119

Difficult

Which statement about installing Schrader valves is correct?


All Schrader cores are suitable for all refrigerants
When brazing the valve body, the core must be removed, then refitted and tightened to the correct torque
Hydrocarbons leak through Schrader valves
Schrader valves must not be used in R744 systems

120

Difficult

How does an undercharge affect the high-pressure side (without discharge pressure control)?


Discharge pressure higher, subcooling higher
Discharge pressure lower, subcooling higher
Discharge pressure higher, subcooling lower
Discharge (condensing) pressure and subcooling will both be lower

121

Difficult

What is the benefit of adding helium as a tracer gas to nitrogen in a pressure test?


Its small atoms pass easily through leaks and are detected
It has a higher pressure than pure nitrogen in the same cylinder
It has a distinctive odour that helps locate the leak
It reacts with refrigerant residues, producing a visible colour change

122

Medium

Who is responsible for keeping the equipment records?


There is no such obligation.
The operator of the unit or system.
The person responsible for risk assessment.
The equipment maintenance technician.

123

Difficult

What can be the effect of a relief valve lifting repeatedly?


The valve no longer opens
The valve may not reseat tightly and its set (opening) pressure may decrease
The valve stays fully open permanently
The set pressure increases

124

Medium

Where are oil traps installed on the suction line?


At the bottom of vertical suction risers with upward flow
At the inlet to every component of the refrigeration system
Before the safety valve on the suction side
Immediately before the compressor suction connection

125

Difficult

What is the relationship between the pressure (p) and temperature (T) of nitrogen at the start (1) and end (2) of a tightness test (p absolute, T in kelvin)?


p₂ = (p₁ × T₂)/T₁
p₂ = T₁/(p₁ × T₂)
p₂ = (p₁ × T₁)/T₂
p₂ = T₂/(p₁ × T₁)

126

Medium

Which symptoms with the compressor running indicate a refrigerant leak (undercharge)?


Sight glass full of liquid and rising oil level in the crankcase
Low suction pressure, high superheat and negligible subcooling
Rising condensing and suction pressures with no superheat
Rising liquid level in the receiver and increasing subcooling

127

Medium

Which components of a refrigeration system are potential leak points subject to leak checks?


Hermetic compressors, liquid receivers and liquid separators
Joints, valves (including stems), seals (including those on replaceable filters and driers), parts subject to vibration and connections to safety and measuring devices
Only high-pressure-side components
Only suction-side components

128

Medium

What pressure is used for the pressure tightness test of an installation?


A pressure equal to the maximum pressure measured during operation
Always 30 bar
A pressure chosen by the technician based on experience
The pressure specified in EN 378-2 or by the manufacturer, not exceeding the maximum allowable pressure of the system (PS)

129

Medium

At which points of the unit must the leak check be carried out?


Only at connections of measuring instruments
At all points where there is a potential risk of refrigerant leakage
Only on discharge-side components
Only on compressor shut-off valves, solenoid valves and filters

130

Medium

When can a unit be considered tight after a pressure test?


When the pressure drop does not exceed 0.1 bar regardless of the test duration
When gas bubbles appear after immersion in water
When it has been checked with a fixed electronic detector
When the pressure remains constant during the test (allowing for temperature-related changes); any unexplained pressure drop requires the leak to be located

131

Medium

Which legal act currently sets out the obligation to check stationary refrigeration equipment containing F-gases for leaks, and how often this must be done?


Regulation (EU) 2024/573
Regulation (EU) No 517/2014
Implementing Regulation (EU) 2024/2215
Commission Regulation (EC) No 1516/2007

132

Difficult

Which parts of a refrigeration system should be given particular attention during a leak check?


Only condenser connections, because the refrigerant is liquid there
Compressor and receiver connections, because the pressure is highest there
Joints, valves incl. stems, seals, parts subject to vibration, connections to safety devices
Only compressor connections, because they are the only parts subject to vibration

133

Easy

What is the superheat of refrigerant vapour?


The difference between the actual vapour temperature and the saturation temperature corresponding to its pressure (expressed in K)
The difference between the condensing temperature and the ambient temperature
The difference between the saturation temperature and the actual liquid temperature in the liquid line
The amount of heat required to evaporate a liquid

134

Difficult

Leak checks can be carried out using various methods. Which pair is correct?


Direct and indirect methods
Material quality control methods and electronic methods
Methods with and without quality control of supplies
Physical and chemical methods

135

Difficult

To whom can leak checks of stationary refrigeration equipment containing F-gases be entrusted?


A person who has carried out such checks before
A natural person holding a certificate covering leak checks (A1, A2 within its charge limit, or E)
An employee appointed by the owner of the installation
Any leak-testing specialist

136

Difficult

What conditions must be met to use UV dye for leak checking?


Manufacturer approval of the method and a certificate covering breaking into the circuit
A UDT authorisation for pressure testing is required
It is sufficient that introducing dye into the circuit is technically feasible
It is sufficient to have a UV lamp, dye and safety goggles

137

Difficult

Which leak-checking methods are considered direct methods?


Pressure-change measurement and immersion in water
1. gas detection devices (portable or fixed leak detection system), 2. UV detection fluid or dye, 3. bubble/foam solutions
Nitrogen with tracer gas and pressure measurement
Vacuum test and foam solution

138

Difficult

What do indirect leak-checking methods involve?


Ultrasonic measurement
Leak detection with UV dye
Leak detection with an electronic detector
A visual and manual check and analysis of parameters: pressure, temperature, compressor current, liquid levels and recharge volume

139

Medium

How should the pressure be increased during a pressure tightness test?


Gradually, in stages, checking for leaks at each level until the test pressure is reached
As quickly as possible
In one step, by fully opening the nitrogen cylinder valve
In any way

140

Medium

What electronic equipment should be used for leak checking?


Only devices with an 'ion pump' sensor
Only hot-cathode devices
Detectors suited to the refrigerant in the system, with appropriate sensitivity, checked periodically
Only detectors with an infrared sensor

141

Medium

What documentation should be checked before starting a leak check?


The equipment records – especially recurring problems and previous leaks
Only the installation invoice and the first start-up report
The operator's fixed-asset inventory ledger
Attendance sheets of the plant-room staff for the year

142

Medium

What information must be recorded in the leak check report?


Date, number and location of leaks, how they were repaired, technician details and signature
Only the number of leaks found and the date of the check
The date, a general note about the leak and the operator's signature
The method used, the time spent on site and the cost of repair

143

Medium

What pressure should be used for the pressure tightness test?


A pressure not exceeding the maximum allowable pressure of the system (PS)
Always 2–3 bar
Any pressure, at the technician's discretion
Always 10–12 bar

144

Medium

What is the temperature glide of a refrigerant?


The temperature drop of the refrigerant across the expansion valve
In zeotropic mixtures, the difference between the temperatures at the start and end of a phase change (boiling or condensation) at constant pressure
The temperature rise of the vapour in the compressor
A property of single-component refrigerants, for which one saturation temperature corresponds to a given pressure

145

Difficult

What does a vacuum (decay) test involve?


With the pump running, you watch the vacuum gauge reading
The pump runs continuously to hold the required vacuum for the test
The pump is restarted every time the system pressure rises
After isolating the pump, you check whether the system pressure rises

146

Difficult

How often should leak tests be carried out on equipment containing 1.5 kg of R404A refrigerant (5.9 tonnes of CO₂ equivalent)?


Once every six months.
On initial commissioning.
Only when servicing the unit.
At least once every 12 months.

147

Difficult

How often should leak tests be carried out on equipment containing 7 kg of R404A refrigerant (27.45 tonnes of CO₂ equivalent)?


At least once every 12 months.
On initial commissioning.
Only when servicing the unit.
Once every six months.

148

Medium

In which equipment is a leakage detection system required?


Equipment with 5 t CO₂ eq or more of F-gases, regardless of equipment type
Equipment with 30 kg or more of F-gases, regardless of their GWP
Equipment with ≥ 500 t CO₂ eq of Annex I F-gases (or ≥ 100 kg of Annex II Section 1 gases)
Equipment with 50 t CO₂ eq or more of F-gases, regardless of equipment type

149

Difficult

Under Regulation (EU) 2024/573, a leakage detection system is mandatory when:


the F-gas charge of the refrigeration equipment is 500 t CO₂ eq or more
the equipment operates in an enclosed space
the equipment contains a flammable refrigerant in any quantity
the charge is 100 kg or more of ozone-depleting substances

150

Difficult

Which leak-checking method may NOT be used by a holder of a Category E certificate?


Checking with a foaming solution
Measurement with a handheld electronic detector
Visual inspection
Leak checking with a fluorescent dye introduced into the circuit

151

Medium

What should you check before using a portable electronic leak detector?


That it has an infrared sensor, as only this type is permitted
That it holds a valid UDT inspection certificate
That it suits the refrigerant and has been checked as the manufacturer requires
That it has been zeroed close to the suspected leak point

152

Medium

Which certificate types (A1, A2, B, C, D, E) authorise leak checks of equipment containing F-gases?


A1, A2 and E
All except D
Only E
Only A1 and A2

153

Difficult

Within what timeframe must a leak test be carried out on a stationary refrigeration system after a leak has been repaired, in accordance with EU Regulation 2024/573 on F-gases?


Immediately after the repair.
Between 24 hours and 1 month after the repair.
At any time.
At the next periodic inspection.

154

Difficult

How often must refrigeration equipment containing ≥500 t CO₂ eq of F-gases be checked if (contrary to Article 6) no leakage detection system is installed?


Every 12 months
Every month
Every 3 months
Every 6 months

155

Medium

Why is it advisable to subcool the liquid refrigerant?


To allow a smaller expansion valve to be used
To ensure that liquid free of vapour bubbles enters the expansion valve
To allow a condenser with a smaller heat-exchange surface to be used
To lower the evaporating temperature in the evaporator

156

Medium

What must be done after repairing a leak in the refrigeration unit of a refrigerated trailer?


Update the equipment records and carry out a leak check (it may be done directly after repair)
Visually inspect only the bolted and brazed joints near the repair
Issue the invoice and leave the leak check to the next periodic service
Charge an alternative refrigerant, start up and measure the parameters

157

Medium

Recovery of fluorinated greenhouse gases means:


The final decommissioning and withdrawal from service or use of a product or piece of equipment containing fluorinated greenhouse gases.
The reprocessing of fluorinated greenhouse gases to achieve their specified standard properties.
The reuse of fluorinated greenhouse gases following a basic purification process.
The collection and storage of fluorinated greenhouse gases from containers, products and equipment during maintenance or servicing or prior to their disposal.

158

Medium

Who is authorised to recover refrigerant from stationary refrigeration equipment containing F-gases?


The owner of the installation
The administrator of the operator's account in the register
A natural person holding a certificate of the relevant type (A1; A2. or D within their charge limit)
The operator

159

Medium

How must recovered refrigerants be stored?


In a disposable (non-refillable) cylinder that held the same refrigerant
In any pressure vessel that has some form of approval
In any used refrigerant cylinder, provided it is leak-tight
In a labelled recovery cylinder with a dual valve and a valid inspection

160

Medium

When should the recovery of fluorinated greenhouse gases be carried out:


Only prior to the final disposal of equipment.
Before each leak test of the equipment.
Always during servicing and maintenance of equipment.
Before the final disposal of equipment and, where applicable, during its servicing and maintenance.

161

Medium

What should be done if recovered refrigerant is contaminated (e.g. with acid, air or moisture)?


Pass it through a particle filter and reuse it
Clean the mixture yourself using a filter-drier
Hand it over to a specialised, authorised company for reclamation or destruction
Add a special contaminant neutraliser

162

Medium

What should be done if different refrigerants have been mixed in a storage cylinder?


Add a special refrigerant to the mixture
Hand the mixture over to an authorised company – as a rule for destruction
Separate the mixture into its components yourself
Pass it through a filter-drier and reuse it

163

Medium

How does push-pull refrigerant recovery work?


The recovery unit draws vapour from the system and condenses it in the cylinder
The recovery unit draws vapour from the recovery cylinder and pushes it into the system; the pressure difference forces liquid refrigerant out of the system into the cylinder
Nitrogen is injected into the system, pushing the refrigerant into the atmosphere
Refrigerant is drawn alternately from the suction and discharge sides of the compressor

164

Medium

What are the options for managing waste refrigerant?


Recycling, reclamation, destruction
Disposal, storage
Recovery, disposal
Reclamation, recovery

165

Medium

Which management option restores recovered refrigerant to a quality equivalent to virgin product, so that it can be used by any undertaking?


Reclamation
Recycling
Destruction
Storage

166

Medium

The lower the evaporating temperature, …


…the greater the density of the suction vapour and the greater the refrigerant mass flow rate
…the lower the density of the suction vapour and the lower the refrigerant mass flow rate
…the greater the density of the suction vapour and the lower the refrigerant mass flow rate
…the lower the density of the suction vapour and the greater the cooling capacity of the compressor

167

Medium

How must transportable pressure vessels (e.g. refrigerant cylinders) be marked?


The marking is optional
Only with weight and capacity marks
With the manufacturer's logo and date of manufacture
Among other things: the number of the design and testing standard, marks of the approving country and the inspection body, the date of the initial inspection, and the manufacturer's and operational marks

168

Medium

The recovery of refrigerants does not require the use of:


Hoses with shut-off valves.
Scales with a measurement range suitable for the size of the cylinder being filled.
A refrigerant recovery station.
An electronic leak detector.

169

Medium

What functions does the compressor perform in a refrigeration system?


The compressor draws in refrigerant vapour from the evaporator, compresses it, and then forces it into the condenser, raising the pressure to the required condensing pressure.
The compressor compresses ambient air and increases the pressure of the refrigerant.
The compressor creates a vacuum on the suction side of the system
The compressor condenses the refrigerant.

170

Easy

What is the compression ratio of a compressor?


The ratio of suction pressure to discharge pressure (po/pc)
The ratio of discharge pressure to the effective capacity of the compressor (p/Vk)
The ratio of absolute discharge pressure to absolute suction pressure (pc/po)
The amount of refrigerant compressed per cycle relative to heat capacity

171

Medium

What is compressor flooding (liquid slugging)?


Liquid refrigerant or oil entering the compression chamber
Excess oil in the condenser
A large amount of liquid refrigerant in a flooded evaporator, which is a normal operating condition
Flooding of the compressor by rainwater

172

Medium

Within what range is the compressor motor speed typically controlled using a frequency inverter?


Speed control does not change the cooling capacity
By a maximum of 10%
Approximately 30 to 75 Hz, corresponding to about 60–150% of nominal capacity (depending on the compressor manufacturer)
From approximately 10% to 90% of nominal capacity

173

Easy

What is the theoretical displacement (swept volume flow) of a compressor?


A value expressed by the coefficient of performance (COP)
The volume of vapour drawn in per unit of time, determined by the compressor's geometry and speed (stated by the manufacturer, e.g. in m³/h)
The volume of refrigerant flowing in one piston cycle under actual operating conditions
The volume of a single cylinder in cm³

174

Medium

Why is it essential to observe the correct phase sequence for scroll compressors and screw compressors?


Because the motor speed would decrease, and consequently the compressor’s capacity.
Because this type of compressor has difficulty starting up if the phase sequence is changed.
Because these types of compressors are sensitive to voltage drops.
Because changing the phase sequence would reverse the direction of rotation of the compressor rotors, which could result in damage to the compressors.

175

Medium

What compression ratio should each stage of a two-stage vapour-compression system have (rule of thumb)?


Equal to 1
Less than approximately 8
Greater than 10
Greater than 18

176

Medium

Why is a shaft seal necessary in open-type compressors?


To protect the crankshaft bearing
Only to prevent oil leakage
To prevent air from entering and refrigerant from leaking out of the compressor
To ensure the bearing remains lubricated

177

Medium

How can you check whether the liquid refrigerant is sufficiently subcooled?


Compare the liquid-line temperature with the saturation temperature at the measured condensing pressure
Check by touch whether the condenser outlet is noticeably colder than ambient
Check whether the whole evaporator surface is covered with an even layer of frost
Check whether the liquid distributor upstream of the evaporator feels warm

178

Medium

Why is the compressor crankcase heated?


To limit refrigerant migration into, and dissolution in, the oil during standstill
To dehydrate the oil
To increase dissolution of refrigerant in the oil and improve its viscosity
To keep the lubricating oil liquid

179

Easy

What is the clearance (dead) volume of a reciprocating compressor?


The space between the side of the piston and the cylinder
The volume between the valve plate and the piston crown at top dead centre
The space between the underside of the piston and the crankcase cover
The volume between the valve plate and the piston at bottom dead centre

180

Medium

What are compressor packs (racks)?


Several air-cooled condensers
Several compressors connected in parallel on a common frame with common suction and discharge headers
Sets of compressors connected in any configuration
Units with two-stage compressors

181

Medium

What is the main advantage of multi-compressor packs?


A smaller refrigerant charge than a single-compressor system
Stepwise capacity matching to demand, plus redundancy
No need for compressor controls and safety devices
Low purchase cost and easy installation without special controls

182

Medium

What is meant by the operating envelope (application range) of a compressor?


A range determined only by the evaporating temperature
The permissible range of evaporating and condensing temperatures (to, tk), or the corresponding pressures, within which the compressor may operate
A range determined by the evaporating temperature at a given ambient temperature
The capacity, refrigerant type and dimensions of the compressor

183

Medium

What are the basic functions of oil in a compressor?


Absorbing moisture from the refrigerant
Increasing the cooling capacity of the refrigerant
Lubricating bearings and sliding surfaces, removing heat, and sealing clearances (e.g. between piston and cylinder, or rotors)
Sealing leaks that develop in the installation

184

Medium

What are the most effective ways of controlling compressor cooling capacity?


Partially covering the evaporator
Changing the displacement: varying the rotational speed or unloading cylinders
An expansion valve
Pressure control valves

185

Medium

What does hot-gas bypass capacity control involve?


High-pressure liquid is injected into the suction to increase capacity
The compressor speed is varied
Bypass is not used for capacity control
Part of the hot discharge gas is passed through a bypass valve to the suction side (or evaporator inlet), reducing the effective capacity

186

Medium

What is the fundamental difference between hermetic and semi-hermetic compressors?


The semi-hermetic compressor has no motor inside the casing
Both can be dismantled; they differ only in cooling capacity
Semi-hermetic compressors run more quietly as a complete unit
The semi-hermetic casing is bolted (can be opened); the hermetic one is welded

187

Medium

How does a scroll compressor work?


It is a positive-displacement compressor in which compression results from the interaction of a fixed and an orbiting scroll.
It uses two screws to compress the refrigerant.
It is a type of piston-type device.
A scroll compressor is also known as a turbo compressor.

188

Medium

What physical process takes place in the evaporator?


The liquid refrigerant evaporates, absorbing heat, and the vapour is slightly superheated at the outlet
The secondary fluid (glycol, water) evaporates while the refrigerant condenses
The refrigerant condenses
The refrigerant is subcooled as a liquid

189

Medium

What is the purpose of compressor capacity control?


To ensure compressor lubrication
To match the cooling capacity to the current demand
To increase the condensing pressure
To match capacity to the condensing temperature

190

Medium

Why is inverter speed control advantageous for refrigeration compressors?


It can be used with any compressor to ensure lubrication
Reducing the speed improves oil return to the compressor
It increases compressor capacity above nominal at any frequency
It enables continuous, smooth control of cooling capacity

191

Medium

Does the suction gas temperature affect the cooling capacity of the compressor?


Yes – higher temperature lowers vapour density, mass flow and capacity
Yes, but only in reciprocating compressors, not scroll
No – capacity depends only on the compressor displacement
Yes, but only if the suction gas is deeply cooled

192

Medium

In the case of compressor units fitted with an oil level control system, is it necessary to install the compressors at the same height?


Yes.
Only screw compressors.
No.
Only scroll compressors.

193

Medium

What functions does a compressor powered by the vehicle’s engine perform in a transport refrigeration system?


This compressor draws in refrigerant vapour from the evaporator, compresses it and then forces it into the condenser whilst the vehicle’s engine is running.
This compressor creates a vacuum on the suction side of the system whilst the vehicle’s engine is switched off.
This compressor condenses the refrigerant whilst the vehicle is in motion.
The compressor compresses ambient air and increases the pressure of the refrigerant.

194

Medium

Which media most commonly absorb heat from the refrigerant in the condenser?


Only a water–glycol mixture
Air and CO₂
Air or water
Ammonia

195

Medium

What is the function of the condenser in refrigeration systems?


Releasing to the environment the heat absorbed in the evaporator and the heat added during compression
Absorption of heat rejected in the regenerative heat exchanger
Releasing only the heat absorbed in the evaporator into the surroundings
Releasing only the heat from the compressor into the surroundings

196

Medium

If the refrigerant temperature on the high-pressure side is above its critical temperature, condensation…


…occurs provided a special condenser is used
…always occurs regardless of temperature
…does not occur
…does not depend on temperature

197

Medium

How is liquid subcooling usually achieved in a refrigeration system?


By dissolving the refrigerant in oil
With an additional heat exchanger using liquid nitrogen
In the final section of the condenser (or in an additional subcooler)
With hot high-pressure vapour

198

Medium

What is the purpose of condenser fan speed control?


To reduce energy efficiency
To disperse refrigerant in the event of a leak
Only to protect against exceeding the maximum condensing pressure
To keep the condensing pressure at the correct level

199

Medium

Which international agreement introduced the global phase-down of HFC production and consumption?


The Paris Agreement
The Kigali Amendment to the Montreal Protocol
The Kyoto Protocol
The Vienna Convention for the Protection of the Ozone Layer

200

Medium

Which international treaty governs the phase-out of ozone-depleting substances (CFCs, HCFCs)?


The UN Framework Convention on Climate Change (UNFCCC)
The Paris Agreement
The Montreal Protocol
The Stockholm Convention

201

Difficult

What is the basis of the GWP values in Regulation (EU) 2024/573?


Each Member State sets its own GWP values
For HFCs (Annex I) – mainly the IPCC Fourth Assessment Report (AR4); for HFOs and non-fluorinated substances (Annexes II and VI) – the Sixth Assessment Report (AR6)
AR4 for all substances
AR6 for all substances

202

Difficult

An air conditioner (not hermetically sealed) contains 2.5 kg of R410A (GWP 2088). How often must it be checked for leaks?


At least every 12 months (5.22 t CO₂ eq)
Every 6 months
No checks required (below 3 kg)
Every 3 months

203

Difficult

When is labelled hermetically sealed equipment containing HFCs (Annex I) exempt from leak checks?


Always, regardless of charge
When it contains less than 10 t CO₂ eq, and in residential buildings also when it contains less than 3 kg of F-gases
When it contains less than 5 t CO₂ eq
Never – hermetically sealed equipment is always checked

204

Difficult

Is a chiller containing 50 kg of R1234ze(E) subject to leak checks under Regulation (EU) 2024/573?


Yes – every 12 months, because its GWP is low
No – the threshold is 5 t CO₂ eq and 50 kg of R1234ze is below 1 t CO₂ eq
Yes – at least every 6 months (every 12 months with a leakage detection system)
No – HFOs are not subject to leak checks

205

Difficult

In 2026, may an existing refrigeration installation using R404A (GWP 3922) be topped up with virgin refrigerant?


Yes, if the equipment has a leakage detection system
No – only reclaimed or recycled R404A is allowed (until 1 January 2030)
Yes – bans apply only to new equipment
Yes – the ban applies only to equipment ≥40 t CO₂ eq

206

Difficult

After 1 January 2026, may an R410A (GWP 2088) air conditioner be serviced using virgin R410A?


Yes – the servicing ban for air conditioners and heat pumps covers F-gases with GWP ≥ 2500
No – the ban covers all refrigerants with GWP ≥ 750
Only with reclaimed refrigerant
No – the ban covers all HFCs

207

Medium

Can HFC refrigerant recovered during a repair be put straight back into the same equipment without any cleaning (filtering/drying)?


Yes, if less than 24 hours have passed
Yes, if the operator agrees
No – recovered F-gas may be used for filling only after it has been recycled or reclaimed
Yes, always

208

Medium

Who may purchase HFCs for servicing refrigeration equipment?


Only the equipment operator
Only a person holding the relevant certificate or an undertaking employing such persons
Any business
Any adult

209

Medium

Under what condition may non-hermetically sealed split air conditioning charged with F-gas be sold to an end user?


When evidence is provided that installation will be carried out by a certified undertaking
Only if the unit contains less than 3 kg of refrigerant
Unconditionally
When the user signs a statement that they will install it themselves

210

Medium

By when must the holder of an F-gas certificate issued under Regulation (EU) No 517/2014 first complete refresher training or an evaluation process?


By 12 March 2029 (and then at least every 7 years)
By 12 March 2025
Never – the certificate is valid indefinitely
By 31 December 2030

211

Medium

What must the holder of a Category I certificate (Regulation 2015/2067) do to continue using it?


Apply for an extension without training
Update their knowledge to the level of Certificate E
Nothing – Category I automatically becomes A1
Update their knowledge and skills to the level of Certificate A1 (Annex I to Regulation 2024/2215)

212

Medium

What does Certificate C under Implementing Regulation (EU) 2024/2215 authorise?


All activities in Article 2(1) in relation to ammonia (NH₃)
All activities in relation to CO₂
Recovery of F-gases from equipment <3 kg
Leak checks without breaking into the circuit

213

Medium

May a person enrolled in a certification training course carry out certified activities?


Yes – with no time limit, if employed by a certified company
No, never
Yes – independently, for 6 months
Yes – under the supervision of a certified person, for no more than 24 months in total

214

Medium

How long must the operator keep the records of equipment subject to leak checks, if they are not kept in a national database?


At least 1 year
Until the equipment is decommissioned
At least 2 years
At least 5 years

215

Difficult

Since 1 January 2025, may a new single-split air conditioner containing 1.5 kg of R410A be placed on the market?


Yes, if the unit is hermetically sealed
Yes – the ban applies only to units >12 kW
No – single splits <3 kg with F-gases of GWP ≥ 750 are banned
Yes – the ban applies from 2029

216

Difficult

From when is it prohibited to place on the market split air-to-air systems up to 12 kW containing F-gases with GWP ≥150 (unless required for safety)?


From 1 January 2025
From 1 January 2029
From 1 January 2027
From 1 January 2035

217

Difficult

Which persistent atmospheric degradation product of R1234yf is classed as a PFAS?


Carbon dioxide
Ozone
Trifluoroacetic acid (TFA)
Carbonic acid

218

Medium

What is floating head pressure and what does it achieve?


It means switching condenser fans off periodically
It lets the condensing pressure fall with ambient temperature, reducing compressor work and raising COP (requires an expansion valve that works at a small pressure difference)
It keeps a constant high condensing pressure all year
It increases subcooling by flooding the condenser

219

Medium

How do SEER/SCOP differ from EER/COP?


SEER/SCOP apply only to natural-refrigerant equipment
EER/COP are always higher than SEER/SCOP
There is no difference – they are synonyms
SEER/SCOP are seasonal indicators accounting for part load and climate (EN 14825); EER/COP refer to a single operating point (EN 14511)

220

Medium

Which design approach can significantly reduce the F-gas charge of a large refrigeration installation?


Larger liquid-line diameters
An indirect (secondary-coolant) system or a cascade with a natural refrigerant in the low stage, plus heat exchangers with small internal volume
Omitting pipe insulation
Adding a second liquid receiver

221

Medium

Which information must be entered in the equipment records after a leak check?


The date and result of the check and the identity of the undertaking and person who performed it (with certificate number)
Only the operator's signature
Only the date of the check
Only the equipment's energy consumption

222

Medium

What must be done when an indirect method (e.g. parameter analysis) indicates a possible leak?


Carry out a direct-method examination to locate the leak
Top up the refrigerant and end the check
Record it and check at the next periodic inspection
Nothing – indirect methods are sufficient