F-Gas English Low GWP
All questions
HFC | Flammable | CO₂ | NH₃
Easy questions |
Medium questions |
Difficult questions
1
Easy
What is the base unit of mass according to the International System of Units (Système International d’Unités)?
| kg |
| Pound |
| N |
| t |
2
Medium
What process takes place in the condenser of a refrigeration system?
| In the condenser, the refrigerant releases the heat absorbed in the evaporator into the surroundings. |
| The medium flowing through the evaporator (glycol, water) condenses, whilst the refrigerant evaporates. |
| Hot refrigerant vapour is pumped from the compressor to the condenser, where it is cooled and then condensed. In this heat exchanger, the resulting liquid refrigerant is also slightly subcooled. |
| The refrigerant releases the heat absorbed in the compressor via the condenser |
3
Medium
What determines the condensation temperature of an air-cooled unit?
| On the ambient temperature. |
| On the evaporation (boiling) temperature. |
| On the compressor and discharge temperatures |
| On the superheat temperature. |
4
Medium
Is energy required when heat is transferred from the condenser to the surroundings?
| The heat flow balances the energy input. |
| Yes, but only when using HFC refrigerants. |
| No, because according to the second law of thermodynamics, thermal energy always flows from a body at a higher temperature to a body at a lower temperature. |
| Yes, in every case. |
5
Medium
What should you pay attention to during the operation of the condenser?
| Care should be taken to ensure that the air temperature at the condenser inlet is lower than the air temperature at the condenser outlet. |
| You should ensure the general maintenance of the condenser and keep the heat exchange surfaces clean. |
| Ensure that the air temperature at the condenser outlet is higher than the condensation temperature. |
| Pay attention to the fan’s operation and the ambient temperature. |
6
Medium
What criteria should be considered when selecting a suitable condenser?
| Condensers should be selected based on your own experience, and the condenser’s geometric parameters should be taken into account. |
| First and foremost, you should consider the operating noise level of the fans, the diameter of the connection pipes and the colour scheme. |
| The required capacity of the condenser and the technical specifications declared by the manufacturer must be taken into account. |
| These include size and the number of fans. The geometric parameters of the condenser must be taken into account. |
7
Medium
How do contaminants (dust, particulates, deposits) affect the performance and efficiency of heat exchange surfaces in condensers?
| Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause an increase in condensing temperature and pressure, which in turn leads to a reduction in the condenser’s efficiency. |
| Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause a reduction in condensing pressure. |
| Contaminants increase the heat transfer area and reduce the condensing pressure. |
| Contaminants do not significantly affect the efficiency and effectiveness of the heat exchange surfaces in condensers. |
8
Medium
If an air-cooled condenser becomes contaminated, will the condensation efficiency?
| It will increase as a result of the fan speed being raised further. |
| It will decrease. |
| It remains unchanged. |
| It will increase. |
9
Medium
What can cause frost to form on the evaporator?
| A reduction in the temperature of the cooled substance. |
| Frost build-up on the evaporator increases airflow resistance and, consequently, causes the fan motor to work harder. |
| a drop in cooling capacity. |
| An increase in refrigerant flow resistance and a reduction in the refrigerant flow rate through the evaporator. |
10
Medium
What happens when the evaporation temperature drops?
| The compressor’s cooling capacity increases. |
| The condenser fan speed increases. |
| The discharge temperature decreases. |
| The compressor’s cooling capacity decreases. |
11
Medium
When is defrosting using the refrigerant possible?
| Never. We use electricity for defrosting (for example, using a special electric heater). |
| Only when using speed-controlled fans. |
| In the case of air-cooled chillers, only when the air temperature is above 0°C. |
| Defrosting using the refrigerant is not possible at all. |
12
Medium
When can frost form on the evaporator surface?
| Only in the case of air coolers, when the air temperature drops below 0°C. |
| In the case of finned evaporators. |
| Frost always forms on air coolers. |
| Frost forms only when the refrigeration system is operating continuously. |
13
Medium
In the case of extensive pipework systems, secondary evaporation of the refrigerant can be prevented by...
| additional cooling. |
| using larger-diameter pipes. |
| by insulating the pipes between the compressor and the condenser. |
| using smaller-diameter pipes. |
14
Medium
How does hot gas defrosting of the evaporator work?
| We swap the outlet and inlet sides of the evaporator. |
| We switch on the gas heater directed at the evaporator. |
| This involves reversing the direction of rotation of the compressor. |
| Heated vapour (hot gas) from the compressor is directed into the evaporator piping. |
15
Medium
What is the function of the evaporator in a refrigeration system?
| It ensures that the refrigerant is superheated over the largest possible heat exchange surface area. |
| It evaporates the water flowing through the evaporator. |
| It cools the refrigerant. |
| Thanks to the evaporator, the cooled medium transfers heat to the boiling refrigerant. |
16
Medium
What conditions must be met for the evaporator to be defrosted using electric heaters?
| The electric heaters must be positioned in direct contact with the refrigerant so that the refrigerant flowing through the evaporator is at a sufficiently high temperature. |
| The electric heaters must be positioned beneath the evaporator’s heat exchange surface. |
| Thanks to the forced air flow created by the fans, the heat from the heaters is transferred to the heat exchanger. |
| The electric heaters must be in contact with the evaporator’s heat exchange surface (the heater must touch the fins). |
17
Medium
Refrigerant distributor:
| ensures the even distribution of the refrigerant discharged by compressors connected in parallel. |
| ensures even distribution of the refrigerant to the individual sections of the condenser. |
| ensures an even distribution of the refrigerant to the individual sections of the evaporator. |
| acts as a buffer for the refrigerant in the event that the pressure upstream of the expansion valve is exceeded. |
18
Medium
What are the possible methods of defrosting air coolers?
| Electric defrosting only. |
| Natural defrosting; there are no other effective methods. |
| Hot gas defrosting. |
| Electric defrosting, liquid defrosting or defrosting using hot refrigerant vapour. |
19
Medium
The boiling point increases (and consequently the rate of evaporation increases) if the pressure above the liquid...
| It behaves differently depending on the ambient temperature. |
| Rises. |
| Falls. |
| Remains constant. |
20
Medium
MOP in thermostatic expansion valves stands for:
| minimum flow opening. |
| maximum pressure switch protection. |
| maximum operating pressure. |
| self-cleaning of the valve in the event of moisture in the refrigerant freezing. |
21
Medium
The function of a thermostatic expansion valve (TEV) in a refrigeration system is:
| to maintain a constant suction pressure to the compressor. |
| to control the amount of refrigerant supplied to the evaporator depending on the superheat of the vapour leaving that heat exchanger. |
| regulating the superheat of the refrigerant leaving the evaporator so that it is at the minimum value. |
| to consistently adjust the evaporation pressure in the condenser depending on the temperature of the refrigerant vapour leaving the condenser. |
22
Medium
When using a capillary tube, what type of motor can be used in the compressor?
| A low-speed motor should be used. |
| A motor with low starting torque can be used. |
| A motor with high starting torque must be used. |
| An electronically commutated motor approved for use with the compressor should be used. |
23
Medium
What does the thermostatic expansion valve regulate?
| Discharge temperature. |
| Cooling. |
| Evaporation pressure after. |
| The mass flow of the refrigerant injected into the evaporator. |
24
Medium
The refrigerant absorbs heat when...
| it evaporates. |
| sublimates |
| it condenses. |
| freezes. |
25
Medium
In the case of a thermostatic expansion valve, the manufacturer specifies...
| ...the static superheat of the valve. |
| ...the superheat value during valve operation. |
| ...the degree to which the valve is filled with refrigerant liquid. |
| …the degree of refrigerant expansion. |
26
Medium
How do we charge a new or repaired system with refrigerant when it is fitted with an expansion valve
| Charging with refrigerant takes place during operation via the outlet connection of the refrigerant capillary tube. |
| in any way. |
| behind the condenser to the liquid refrigerant receiver. |
| to the suction side of the compressor. |
27
Medium
What does a thermostatic/electronic expansion valve regulate?
| The number of revolutions of the compressor per unit of time. |
| The evaporation pressure, closing when it falls below the setpoint temperature. |
| Condenser subcooling by adjusting the condensing pressure. |
| The amount of refrigerant by controlling the evaporator superheat. |
28
Medium
What does the MOP function in expansion valves mean?
| This means that these expansion valves are set to prevent overheating. |
| This means that these expansion valves are set to limit subcooling. |
| This means that these expansion valves are set to a specific suction pressure. |
| It means that these expansion valves are set to limit the maximum operating pressure. |
29
Medium
The lower the temperature of the liquid refrigerant upstream of the expansion valve,
| ...the lower the theoretical coefficient of cooling efficiency qo will be, and the lower the system’s energy efficiency will be. |
| ... the higher the theoretical coefficient of cooling capacity qo will be, and the greater the cooling capacity Qo will be. |
| ...the lower the theoretical coefficient of cooling efficiency qo will be, whilst the cooling capacity Qo remains unchanged. |
| ...the lower the theoretical coefficient of refrigeration efficiency qo will be, and the lower the refrigeration capacity Qo will be. |
30
Medium
The MOP point in the expansion valve, due to the maximum evaporation temperature of the refrigeration system, ...
| ...must be approximately 5 K lower. |
| The value of the MOP point is irrelevant. |
| ...must be approximately 7 K lower. |
| ...must be approximately 7 K higher. |
31
Medium
What is the function of the suction pressure regulator?
| It prevents a drop in suction pressure and, if necessary, shuts down the refrigeration system. |
| To maintain the suction pressure at the highest possible level. |
| It maintains the suction pressure at a constant level. |
| It limits the suction pressure and protects the compressor from excessively high suction pressure. |
32
Medium
What is the function of the valve regulating water flow through the condenser?
| To maintain the condensing pressure at a constant level. |
| To maintain the condensing pressure at the highest possible level. |
| To maintain the condensing pressure at the lowest possible level. |
| To maintain the water temperature at the highest level. |
33
Medium
The use of a refrigerant distributor requires a thermostatic expansion valve …
| … with an adsorption-type sensor filling. |
| … with internal pressure equalisation. |
| … with a MOP function. |
| … with external pressure equalisation. |
34
Medium
What properties should good insulation materials have?
| It must have a high thermal conductivity. |
| It must have a good antistatic coating |
| It must be able to absorb large amounts of moisture. |
| It must have a low thermal conductivity. |
35
Medium
When do we encounter the superheated state?
| This is the temperature difference between the actual vapour temperature and the vapour temperature at saturation. |
| This is a state that arises as a result of the temperature difference between the suction side and the discharge side of a compressor. |
| It is a condition in which the compressor motor temperature rises excessively. |
| It is the temperature difference between the evaporation temperature and the ambient temperature. |
36
Medium
How can you check whether the liquid refrigerant is reaching the expansion valve without vapour bubbles?
| We check using a liquid pressure gauge. |
| We check using a pressure gauge fitted on the discharge side of the compressor. |
| We check this using a sight glass. |
| We are unable to check this. |
37
Medium
The liquid lines are located...
| between the condenser and the liquid receiver. |
| between the evaporator and the compressor. |
| between the evaporator and the regenerative heat exchanger. |
| between the compressor and the condenser. |
38
Medium
What is the function of the liquid receiver in a refrigeration system?
| The reservoir is used to further cool the liquefied refrigerant leaving the condenser. |
| The tank is used to store and ensure an adequate supply of refrigerant in the event of fluctuations in the thermal load of the refrigeration system. |
| When an installation technician does not know the exact amount of refrigerant required, the tank serves as a safety reserve for the entire refrigeration system. |
| The tank is used to collect the liquid refrigerant and excess oil in the system. |
39
Medium
What is the purpose of the liquid refrigerant reservoir?
| The tank is used to further cool the liquefied refrigerant leaving the condenser. |
| When an installation technician does not know the exact amount of refrigerant required, the tank serves as a safety reserve for the entire refrigeration system. |
| The tank is required during maintenance work, when there is a temporary need to store the refrigerant that has been circulating in the refrigeration system up to that point. |
| The tank is used to collect the liquid refrigerant and excess oil in the system. |
40
Medium
Where should the liquid receiver be installed?
| It should be fitted after the evaporator. |
| It should be fitted between the compressor and the condenser. |
| It should be installed downstream of the condenser, upstream of the expansion valve. |
| It should be fitted just before the compressor. |
41
Medium
What is the function of the suction pressure regulator fitted to the suction pipe when the compressor starts up?
| It regulates the condensing pressure. |
| It regulates the evaporation pressure. |
| It opens when the suction pressure upstream of the compressor drops. |
| It closes when the suction pressure upstream of the compressor drops. |
42
Medium
The use of microchannel heat exchangers, compared with conventional heat exchangers made of copper tubes and fins, results in:
| There is no effect whatsoever on either the amount of refrigerant or energy efficiency. |
| A reduction in the amount of refrigerant and an increase in energy efficiency. |
| An increase in the amount of refrigerant in the system and an increase in condensing pressure. |
| A reduction in the system’s energy efficiency. |
43
Medium
Which refrigerants belong to the HFC group?
| R11, R12, R502. |
| R134a, R404A, R507A, R410A. |
| R22, R401A. |
| R134a, R32, R22, R507A, R290. |
44
Medium
Which refrigerants belong to the HFO group?
| R1234yf, R1234ze. |
| R134a, R290. |
| R22, R12. |
| R134a, R404A. |
45
Medium
What are the characteristics of R410A refrigerant compared to R407C refrigerant?
| The saturation pressure of both refrigerants is roughly the same. |
| The saturation pressure of R407C is 150% higher than that of R410A. |
| The saturation pressure of R407C refrigerant is much higher than that of R410A. |
| The saturation pressure of R410A refrigerant is higher than that of R407C. |
46
Medium
What does the TEWI parameter define?
| It is the global warming potential, expressed in terms of carbon dioxide (CO₂), over a 100-year time horizon. |
| This is a parameter that quantifies the impact of refrigerants on the ozone layer. |
| It is the total (global) greenhouse gas equivalent – this indicator takes into account the refrigerant’s direct capacity to contribute to the greenhouse effect and its indirect impact on it through the energy consumption (during the production of which CO₂ is generated) by the refrigeration unit in operation. |
| This is a parameter defining the ozone layer’s ability to recover (regenerate). |
47
Medium
What are the characteristics of R452A refrigerant compared to R404A?
| It is a non-flammable refrigerant, a mixture from the HFC/HFO group with thermodynamic properties similar to those of R404A and a GWP approximately 45% lower than that of R404A. |
| It is a flammable and toxic homogeneous refrigerant from the HFC group. |
| The temperature glide of R452A is half that of R404A. |
| Both refrigerants are homogeneous refrigerants with no temperature glide. |
48
Medium
What is the distinguishing feature of R1234yf compared to R134a?
| a higher boiling point at standard pressure. |
| A higher critical temperature. |
| greater flammability. |
| greater toxicity. |
49
Medium
Compared to R134a, the refrigerant CO₂ is characterised by?
| It has a temperature slip of 7K greater than R134a. |
| Unlike R134a, it is an azeotropic mixture. |
| It has a lower critical temperature, higher operating pressures and greater volumetric efficiency, allowing for the use of a smaller quantity of refrigerant compared to R134a. |
| It has identical thermodynamic properties and can be used as a drop-in replacement for R134a. |
50
Medium
The following are not classified as fluorinated greenhouse gases:
| Hydrofluorocarbons (HFCs). |
| Perfluorocarbons (PFCs). |
| Carbon dioxide (CO₂). |
| Sulphur hexafluoride (SF6). |
51
Medium
What is the greenhouse effect?
| It causes an increase in temperature close to the Earth’s surface (up to 10 metres above the surface). |
| It alters the composition of the atmospheric air. |
| It lowers the average surface temperature of the Earth. |
| It causes the thermal radiation emitted by the Earth to be trapped in the upper atmosphere. |
52
Easy
What does the GWP indicator mean?
| It is an expansion of the abbreviation ‘Global Warming Potential’ and indicates the rate of increase in air temperature |
| It is a unit expressing the ability to enhance the ozone layer. |
| This is an indicator expressing the potential to deplete the ozone layer. |
| It is the global warming potential. The impact on global warming caused by 1 kg of a given gas or chemical substance, expressed as a GWP value, where GWP=1 represents the global warming caused by 1 kg of CO₂ over a period of 100 years (the global warming potential of a unit mass of a given gas over a 100-year period, relative to the warming caused by a unit mass of CO₂). |
53
Medium
How do refrigeration systems contribute to the greenhouse effect, i.e. the rise in atmospheric temperature at the Earth’s surface?
| As a result of oil being emitted into the atmosphere by the condenser and filter |
| Through the leakage of refrigerant into the environment. |
| Indirectly (through energy consumption) and directly (through the emission of refrigerants into the atmosphere) |
| Refrigeration equipment emits CO₂ both directly and indirectly. |
54
Medium
What is the greenhouse effect, also known as the greenhouse phenomenon?
| The absorption of radiation reaching the Earth’s surface. |
| The filtering out of solar radiation. |
| It is the phenomenon of heat being trapped in the Earth’s atmosphere (making it difficult for heat to radiate out of the Earth’s atmosphere). |
| This is the formation of a layer that traps only the heat generated by the combustion of fuel in aeroplanes. |
55
Medium
Which EU regulation is currently the primary piece of legislation governing the use of fluorinated greenhouse gases (F-gases) in the European Union?
| Directive 2009/125/EC |
| Regulation (EU) 2015/1188 |
| Regulation (EU) No 517/2014 |
| Regulation (EU) 2024/573 |
56
Medium
What is the main objective of Regulation (EU) 2024/573?
| Standardising metal recycling standards |
| To reduce taxes on refrigeration equipment |
| To facilitate the import of electrical appliances |
| Prevention of F-gas emissions and the achievement of the EU’s climate targets |
57
Medium
What are the obligations of manufacturers of refrigeration appliances in the context of ecodesign, and which regulation governs them?
| The manufacturer must ensure minimum energy efficiency, reparability and recyclability of equipment, as regulated by Regulation (EU) 2019/2019 |
| Manufacturers are only required to declare the quantity of F-gas used, in accordance with Regulation (EU) No 517/2014 |
| Manufacturers must comply solely with ISO 9001 standards, without any link to EU regulations |
| Manufacturers are only required to use energy labels, and this is regulated by Regulation (EU) 2024/573 |
58
Medium
What is the main objective of the Ecodesign Directive?
| To standardise the appearance of products in the EU |
| To facilitate the import of products from outside the EU |
| To increase sales of electrical appliances in the EU |
| Reducing the negative environmental impact of products by improving energy efficiency, durability and recyclability |
59
Medium
What is the function of a ball valve in a refrigeration system?
| It prevents excessive pressure build-up in the system |
| Enables the refrigerant flow to be completely shut off |
| It regulates the temperature of the refrigerant |
| It measures the moisture content of the refrigerant |
60
Easy
What is the main function of a relief valve?
| It controls the oil level in the compressor |
| Relieves pressure in the system in the event of excessive pressure |
| Prevents the evaporator from freezing |
| It monitors the moisture content of the refrigerant |
61
Medium
How do certain substances or gases contribute to the greenhouse effect?
| Some substances damage the ozone layer |
| Certain substances limit the impact of the Sun’s ultraviolet radiation on the Earth’s surface. |
| Certain substances trap the thermal radiation that the Earth should radiate into the atmosphere. In this way, the Earth gradually warms up and the greenhouse effect occurs. |
| When released into the atmosphere, certain substances cause the air to heat up as a result of reactions with the oxygen and nitrogen contained in the air. |
62
Medium
What is the purpose of the sight glass in a refrigeration system?
| To shut off the flow in the event of an emergency |
| To regulate compressor pressure |
| For visual assessment of the presence of refrigerant and oil, and for monitoring moisture levels |
| To measure the condenser temperature |
63
Medium
What is the function of the temperature regulator in a refrigeration system?
| It restricts oil flow |
| Controls the operation of the compressor and valves to maintain the set temperature |
| To maintain a constant pressure in the compressor |
| It drains excess refrigerant into the receiver |
64
Difficult
What is the role of the liquid separator in systems using flammable or toxic refrigerants?
| It separates the liquid from the oil |
| They are used solely to measure the moisture content of the refrigerant |
| Heats the refrigerant before it enters the evaporator |
| It prevents liquid from entering the compressor |
65
Difficult
What is the function of an oil separator in systems using flammable or toxic refrigerants?
| Heats the refrigerant before it enters the evaporator |
| Separates oil from the refrigerant and facilitates the return of oil to the compressor |
| It prevents liquid from entering the compressor |
| They are used solely to measure the moisture content of the refrigerant |
66
Medium
What is the purpose of oil level regulators in a refrigeration system?
| They control the pressure in the condenser |
| They control the evaporator temperature |
| They drain off excess refrigerant |
| Maintains the correct oil level in the compressor |
67
Medium
What is the function of the refrigerant receiver in the system?
| It maintains a constant pressure in the system |
| Stores excess refrigerant and facilitates the detection of leaks |
| Regulates the oil flow |
| It controls the evaporator temperature |
68
Medium
What is the role of the manifold thermometer in the refrigeration system?
| Controls the oil level |
| Measures the refrigerant temperature at the compressor inlet and outlet, which helps to identify leaks |
| Relieves pressure in the system in the event of excessive pressure |
| It monitors the moisture content of the refrigerant |
69
Medium
What is the role of the defrost control valves?
| Protect the evaporator from excessive icing and reduce the risk of leaks |
| They are used to monitor the moisture content of the refrigerant |
| They drain off excess oil |
| They control the pressure in the compressor |
70
Easy
What is the base unit of pressure according to the International System of Units (SI)?
| Pa |
| Psi |
| bar |
| Atm. |
71
Medium
Where can I find lists detailing fluorinated greenhouse gases (F-gases)?
| In the Act on Ozone-Depleting Substances and Certain Fluorinated Greenhouse Gases. |
| In Regulation (EU) No 2024/573 of the European Parliament and of the Council |
| In the Regulation of the Minister for the Economy on the introduction of a list of fluorinated greenhouse gases. |
| In the Vienna Convention for the Protection of the Ozone Layer. |
72
Medium
Where can I find the lists specifying controlled substances?
| In the Regulation of the Minister for the Environment on the list of controlled substances. |
| In the current Act on Ozone-Depleting Substances and Certain Fluorinated Greenhouse Gases. |
| In Regulation (EU) No 2024/590 of the European Parliament and of the Council. |
| In the Vienna Convention for the Protection of the Ozone Layer. |
73
Medium
Where and by when should annual reports on ODS and F-gases be submitted?
| Reports for the previous year must be submitted by 31 March of the relevant year electronically to the Ministry of the Environment. |
| Reports for the previous year must be submitted by 31 January electronically by completing the special forms available in the central register of operators ‘CRO’. |
| Reports must be submitted by the end of the relevant calendar year, using a special form at the regional branch of the Office of Technical Inspection (UDT) |
| Reports on ODS and F-gases for the previous year must be submitted by 28 February of the following year, via the IT system available in the reports database at the Office for the Protection of the Ozone Layer and Climate (BOWOiK) on the ICHP website. |
74
Medium
Which measure has the greatest impact on improving the compressor’s energy efficiency during installation?
| Installation without filters |
| Installation without a leak test |
| Increasing the amount of refrigerant |
| Correctly create a vacuum and remove moisture from the system |
75
Medium
How does regular monitoring of the oil level affect the compressor’s operation?
| Ensures proper lubrication and improves energy efficiency |
| It reduces cooling capacity |
| Causes a rise in pressure |
| It has no effect |
76
Medium
How do system leaks affect the compressor’s energy efficiency?
| These cause a drop in performance and an increase in energy consumption |
| Have no effect |
| They improve efficiency |
| They lower the operating temperature |
77
Medium
Regulation (EC) No 2024/590 relates to:
| Alternative refrigerants serving as substitutes for fluorinated greenhouse gases. |
| The conditions for obtaining F-gas certificates by companies carrying out the recovery and reclamation of waste refrigerants. |
| Ozone-depleting substances. |
| Health and safety at work during the recovery of refrigerants. |
78
Medium
What is the significance of regulating suction and discharge pressure?
| Causes leaks |
| Increases oil consumption |
| It has no effect on efficiency |
| Helps maintain optimal operating conditions for the compressor |
79
Medium
What maintenance measure reduces the compressor’s energy consumption?
| Regular replacement of filters and dryers |
| Disabling safety devices |
| Increasing the refrigerant charge |
| Lack of servicing |
80
Medium
How does the presence of air in the refrigeration system affect performance?
| Reduces energy consumption |
| It improves efficiency |
| Leads to increased pressure and reduced efficiency |
| It has no effect |
81
Medium
What role do control systems (e.g. regulators) play in compressor efficiency?
| It doesn’t matter |
| It increases the amount of refrigerant |
| Causes leaks |
| Enables optimisation of operation and a reduction in energy consumption |
82
Medium
How does refrigerant superheat at the compressor suction affect performance?
| It always improves performance |
| It only causes a drop in temperature |
| It has no effect |
| Excessive overheating reduces efficiency and increases energy consumption |
83
Medium
How does the correct layout of the system affect efficiency?
| It causes the temperature to rise |
| Shortens flow paths and reduces energy losses |
| It doesn’t matter |
| It increases the pressure |
84
Medium
How important is pipe insulation?
| It increases energy consumption |
| Reduces heat loss and improves energy efficiency |
| It has no effect |
| Causes a rise in pressure |
85
Medium
Which measure most improves the condenser’s energy efficiency?
| Increasing the amount of refrigerant |
| Restricted airflow |
| Regular cleaning of heat exchange surfaces |
| Contamination of the heat exchange surface |
86
Medium
How does a dirty condenser affect the operation of the refrigeration system?
| Causes an increase in pressure and energy consumption by the compressor |
| It lowers the condensing pressure |
| It has no effect |
| It improves efficiency |
87
Medium
Why is adequate airflow through an air-cooled condenser important?
| Ensures effective heat dissipation and improves energy efficiency |
| It doesn’t matter |
| Causes a drop in pressure |
| Insufficient airflow reduces efficiency |
88
Medium
Which refrigerants cause damage to the ozone layer?
| All refrigerants that contain fluorine and hydrogen in their molecules. |
| All refrigerants that are hydrocarbon derivatives. |
| All refrigerants that contain chlorine or bromine in their molecules. |
| All refrigerants that contain carbon in their molecular structure. |
89
Medium
How does the presence of limescale in a water-cooled condenser affect performance?
| It lowers the condensation temperature |
| Impairs heat exchange and increases energy consumption |
| It improves heat transfer |
| It has no effect |
90
Medium
How does correct condensation pressure control affect efficiency?
| It has no effect |
| It increases energy consumption |
| Maintains optimum operating conditions and reduces energy consumption |
| Causes leaks |
91
Medium
How do condenser leaks affect energy efficiency?
| Causes refrigerant loss and a drop in efficiency |
| Have no effect |
| They lower the temperature |
| They improve efficiency |
92
Medium
How important is the correct positioning of an air-cooled condenser?
| It should be installed in a well-ventilated area with unobstructed airflow |
| It doesn’t matter |
| It should be housed in a small room |
| It should be close to heat sources |
93
Medium
How does hot air recirculation affect the condenser?
| It has no effect |
| It improves efficiency |
| It reduces the pressure |
| Impairs cooling and increases energy consumption |
94
Medium
How does the insulation of central heating and domestic hot water pipework affect the operation of the heat pump’s condenser?
| It increases the pressure |
| Reduces energy losses and improves the efficiency of the entire system |
| It impairs cooling |
| It doesn’t matter |
95
Medium
Which measure most improves the energy efficiency of the evaporator?
| Regular defrosting of the evaporator |
| Increasing the amount of refrigerant |
| Increasing the condensation temperature |
| Restricted airflow |
96
Medium
How does evaporator icing affect the system’s operation?
| It has no effect |
| It lowers the condensation temperature |
| Impairs heat exchange and increases energy consumption |
| It improves cooling performance |
97
Medium
How does dirt on the evaporator surface affect its performance?
| It improves efficiency |
| Impairs heat exchange and increases energy consumption |
| It has no effect |
| It reduces the pressure |
98
Medium
What maintenance task is crucial for the evaporator?
| Regular cleaning and defrosting |
| Lack of maintenance |
| Reduced airflow |
| Increasing the refrigerant charge |
99
Medium
What does an F-gas personal certificate (Category A2) authorise?
| for the purchase of lubricants and refrigeration oils, and for the testing of safety valves. |
| to repair, maintain or service refrigeration equipment and systems containing controlled substances. |
| To recover refrigerant from equipment containing less than 3 kg of fluorinated greenhouse gases, or less than 6 kg in the case of hermetically sealed systems. |
| to make permanent joints by brazing in systems containing fluorinated greenhouse gases. |
100
Medium
How does superheating of the refrigerant at the evaporator outlet affect efficiency?
| Excessive superheat reduces energy efficiency |
| It always improves performance |
| It only causes a drop in temperature |
| It has no effect |
101
Medium
How do leaks in the evaporator affect efficiency?
| Increase capacity |
| These cause refrigerant loss and a drop in efficiency |
| Improves performance |
| Have no effect |
102
Medium
How important is correct expansion valve adjustment?
| It doesn’t matter |
| Ensures optimal evaporator charge and improves efficiency |
| Causes leaks |
| It increases energy consumption |
103
Medium
How does inadequate insulation of the heat transfer circuit pipes affect evaporator performance?
| It lowers the condensation temperature |
| Causes cooling losses and increased energy consumption |
| It has no effect |
| It improves efficiency |
104
Medium
How does correct TEV valve adjustment affect the system’s energy efficiency?
| It has no effect |
| Ensures optimum superheat and improves system efficiency |
| It increases energy consumption |
| Causes leaks |
105
Medium
What happens if the superheat set by the TEV is too high?
| Efficiency will drop because the evaporator is not being fully utilised |
| The refrigerant charge will increase |
| Cooling efficiency will improve |
| It has no effect |
106
Medium
How does a low superheat setting on the TEV affect performance?
| It has no effect |
| It increases operational safety |
| It reduces refrigerant flow |
| It may lead to improved efficiency, but it increases the risk of the compressor becoming flooded with liquid |
107
Medium
How do contaminants in the system affect the operation of the TEV?
| They can cause it to become blocked and reduce efficiency |
| Have no effect |
| They lower the temperature |
| They improve its performance |
108
Medium
What role does the filter-drier play in terms of system efficiency?
| It doesn’t matter |
| It lowers the temperature |
| Removes moisture and contaminants, improving the system’s efficiency |
| It increases the amount of refrigerant |
109
Medium
How does proper insulation of components (e.g. pipes near the TEV) affect the system?
| It doesn’t matter |
| It increases energy consumption |
| It causes leaks |
| Prevents unwanted heat gains and improves efficiency |
110
Medium
What does Regulation (EU) No 2024/573 of the European Parliament and of the Council cover?
| The Regulation concerns gases that contribute to the greenhouse effect. |
| The Regulation sets out health and safety requirements for soldering work. |
| The Regulation concerns leak testing of stationary refrigeration, air-conditioning and heat pump equipment containing fluorinated greenhouse gases. The Regulation sets out the requirements relating to leak testing of such equipment. |
| The Regulation sets out requirements relating to brazing of refrigeration systems. |
111
Medium
How important is it to check the operation of the condensing pressure control valve in the system?
| It causes a significant rise in temperature |
| It increases energy consumption |
| Ensures operation within the optimum pressure range and reduces energy losses |
| It has no effect |
112
Medium
How does the correct selection of a TEV affect energy efficiency?
| Ensures the system is matched to its capacity and operates optimally |
| It doesn’t matter |
| It lowers the temperature |
| It increases the amount of refrigerant |
113
Medium
What is the main design difference in hydrocarbon-based refrigeration systems?
| Higher operating pressures |
| The need for explosion-proof measures due to the flammability of the refrigerant |
| No need for safety measures |
| Lower energy efficiency |
114
Medium
What differences are there in the compressors used in hydrocarbon systems?
| They do not require lubrication |
| They must operate at higher pressures |
| No differences |
| They must be designed to operate with flammable refrigerants (e.g. hermetic compressors) |
115
Medium
How can one check whether the system has been overcharged with refrigerant?
| This cannot be checked with sufficient reliability, as the sight glass is not designed for this purpose. |
| The refrigeration system is overcharged with refrigerant whilst in operation, and even under a very small heat load, frost forms on the suction side of the compressor |
| Under normal conditions, there is a marked increase in condensing pressure because an excessive amount of refrigerant accumulates in the condenser, reducing the heat exchange surface area within it. |
| The compressor will operate under a lower load and the suction pressure will decrease |
116
Medium
Before charging the refrigeration unit with refrigerant, it is essential to…
| carry out a leak test. |
| complete the unit’s data sheet. |
| carry out a start-up test. |
| check the compressor’s suction and discharge connections. |
117
Medium
What information must appear on the unit’s label?
| It does not matter what should be included on the device label. |
| The manufacturer’s logo and the weight of the unit. |
| Markings regarding the weight and capacity of the pipework, together with the colour code and chemical composition of the paints used to coat the frame and casing. |
| Among other things: information stating that the unit contains a fluorinated greenhouse gas, together with the industrial designation of the gas or its chemical name, the mass of the gas and its CO₂ equivalent |
118
Medium
What is the base unit of temperature according to the International System of Units (Système International d’Unités)?
| °R |
| K |
| °C |
| °F |
119
Medium
Which of the following are the most important pieces of information that should be included in the unit’s data sheet:
| Operator details, unit details, type and quantity of refrigerant, information regarding servicing and repairs. |
| Information regarding refrigerant recovery and unit dismantling. |
| The make and model of the unit, so that the manufacturer can be contacted to obtain the technical information necessary for servicing. |
| The owner, installer and service technician of the unit. |
120
Medium
Who is responsible for drawing up the equipment or installation record?
| The equipment maintenance technician. |
| The operator of the unit or system. |
| There is no such obligation. |
| The person responsible for risk assessment. |
121
Medium
Oil traps on the suction pipework are required:
| always before any rise in the pipeline. |
| before the safety valve. |
| at the inlet to each component of the refrigeration system. |
| before the compressor. |
122
Medium
When is there a refrigerant leak, even though the compressor is still running?
| When the condensing pressure and suction pressure rise, but there is no superheat. |
| When the suction pressure is low, superheat is high, subcooling is negligible and the temperature difference between the condenser and the expansion valve is small. |
| When we observe a rise in the refrigerant level in the liquid receiver and the subcooling increases. |
| When the sight glass is full of liquid refrigerant and we observe a rise in the oil level in the compressor sump. |
123
Medium
Which components of a refrigeration system can be classified as potential leak points (leaks) subject to regular leak tests?
| Hermetic compressors, liquid refrigerant tanks and liquid separators. |
| Parts of the system located on the high-pressure side (from the compressor up to and including the expansion valve). |
| All parts of the refrigeration unit that are connected to the suction side of the refrigeration system. |
| Fittings, valves including their stems, seals – including those in replaceable filters and dryers, components exposed to vibration, and connections to measuring, control and safety devices. |
124
Medium
What is the test pressure during the pressure leak test of the unit?
| The test pressure for leak testing is equivalent to the maximum operating pressure measured during the operation of the refrigeration unit. |
| The test pressure is determined by the person carrying out the leak test based on their experience. |
| The test pressure (maximum) is 30 bar. |
| According to the PN-EN 378 standard, at least 0.25 times the maximum permissible pressure for the system (PS). |
125
Medium
In which part of the refrigeration unit must the recommended leak test be carried out?
| The check must be carried out on all parts of the refrigeration system that are connected to the discharge side of the refrigeration circuit. |
| The check should only be carried out at the connection points for measuring instruments (pressure switches, pressure gauges, temperature sensors). |
| The test must be carried out on the compressor shut-off valves, solenoid valves and filters. |
| The test must be carried out at all points on the refrigeration unit where there is a potential risk of refrigerant leakage. |
126
Medium
When can a given unit be considered perfectly leak-tight?
| The device in question is perfectly leak-tight when we have carried out a check using a permanently installed electronic detector. |
| A given unit can be considered perfectly leak-tight if, during a leak test, the pressure remains constant, taking into account pressure changes caused by temperature variations. Any drop in pressure indicates a leak and requires the location of the leak to be identified. |
| A given device can be considered perfectly leak-tight when the pressure drop during the test does not exceed 0.1 bar. |
| A device can be considered perfectly leak-tight if gas bubbles appear when it is submerged in water. |
127
Medium
What does EU Regulation 1516/2007 cover?
| The Regulation sets out health and safety requirements for soldering work. |
| The Regulation sets out requirements relating to brazing of refrigeration systems. |
| The Regulation concerns leak testing of stationary refrigeration, air-conditioning and heat pump equipment containing fluorinated greenhouse gases. The Regulation sets out the requirements for leak testing of such equipment. |
| The Regulation addresses the disposal of gases that contribute to the greenhouse effect. |
128
Difficult
Which parts of refrigeration systems must be inspected on a mandatory and regular basis in accordance with EU Regulation 1516/2007?
| Only compressor connections, as these are subject to vibration. |
| Compressor connections, 2. connections on the liquid refrigerant tank |
| Fittings, 2. valves, 3. seals, 4. parts/components exposed to vibration, 5. connections at safety devices. |
| Connections on the condenser, as there is high pressure and the refrigerant is in liquid form |
129
Easy
What is superheat?
| It is the amount of heat required to increase the pressure. |
| It is the amount of heat required to turn a liquid into vapour. |
| It is the amount of heat required to cause the vapour formed from a liquid to become superheated. |
| It is the amount of heat required to heat a liquid. |
130
Difficult
In accordance with EU Regulation 1516/2007, there are several methods of leak testing. What are these methods called?
| We distinguish between physical and chemical methods. |
| We distinguish between methods for quality control of supplied materials and leak testing methods that do not involve quality control of supplied materials. |
| We distinguish between quality control methods for supplied materials and electronic testing methods. |
| We distinguish between direct and indirect methods of leak detection. |
131
Difficult
In accordance with EU Regulation 1516/2007, to whom can we entrust the responsibilities for leak testing of refrigeration systems?
| The check may only be carried out by a person who has previously carried out such a check. |
| The inspection may be carried out by a person employed and appointed by the owner of the installation. |
| The test may only be carried out by a competent person with the relevant skills, who holds a certificate attesting to the necessary knowledge in this field. They must also hold a certificate for companies regarding the operation and maintenance of refrigeration equipment charged with F-gases. |
| The check may be carried out by a specialist in leak testing. |
132
Difficult
In accordance with EU Regulation 1516/2007, what conditions must be met in order to carry out a leak test on refrigeration systems using ultraviolet (UV) light?
| A prerequisite for carrying out a leak test using UV is having the appropriate technical resources, the relevant materials supplied, and suitable safety goggles. |
| The manufacturer of the refrigeration equipment must confirm that the aforementioned UV method can be used. A UV leak test may be carried out by a qualified person who holds the relevant qualifications (certificate). |
| A prerequisite for carrying out a leak test using UV is that such a test is technically feasible. |
| A prerequisite for carrying out the inspection is holding the relevant authorisation for pressure testing issued by the UDT. |
133
Difficult
In accordance with EU Regulation 1516/2007, which leak testing methods are classified as direct leak testing methods?
| Leak testing by measuring pressure changes and the method of submerging the device/system in water. |
| Detection of leaks using a handheld leak detector and/or a fixed leak detection system; 2. Detection of leaks using a special dye with UV-fluorescent properties; 3. Detection of leaks using a foaming solution. |
| Leak test using nitrogen with a tracer gas, an electronic detector and pressure measurement. |
| Leak test following the creation of a vacuum and leak detection using a foaming solution. |
134
Difficult
In accordance with EU Regulation 1516/2007, which methods are classified as indirect leak testing methods?
| It utilises pressure and temperature measurements, as well as an ultrasonic method. |
| This method is based on electronic leak detection. |
| Leak detection using a UV tracer. |
| This method is based on the analysis of the following parameters: pressure, temperature, operating pressure, liquid level, oil leakage, etc. |
135
Medium
How should the pressure be increased during a pressure leak test?
| We increase the pressure at a rate of 10 bar/s. |
| We increase the pressure in any way. |
| We increase the pressure as quickly as possible. |
| We increase the pressure gradually whilst checking for leaks, until the test pressure is reached, at a rate of no more than 2 bar/min |
136
Medium
What electronic equipment should be used to carry out leak testing?
| Only with devices fitted with hot cathodes. |
| Only using devices with verified measurement sensitivity. |
| Only with devices fitted with an ‘Ion Pump’ sensor. |
| Only with devices fitted with an infrared detector. |
137
Medium
What documentation should be checked before starting a leak test?
| Check the operating instructions for the machine/equipment. |
| Check the stock ledger (accounts). |
| Check the time sheets of the staff responsible for the machinery/equipment. |
| The maintenance log and the machine/device operating instructions must be checked. |
138
Medium
What information must be recorded when drawing up the leak test report?
| The method used to carry out the leak test, the number of faults, the method of repairing the faults, the time taken to work on the installation, and the cost of the repair. |
| The date of the inspection, the number of faults (leaks), the location of the faults (leaks), the proposed method of rectifying the fault/defect (leak), attached documents and a signature. |
| The number of locations where leaks have occurred and the date of the inspection. |
| The date of the inspection, a record of the occurrence of the leak, and a signature. |
139
Medium
What pressure values should be used for the pressure leak test?
| At the discretion of the person authorised to carry out the pressure test. |
| The pressure value for the leak test is 10–12 bar. |
| Use a pressure not exceeding the maximum permissible pressure for the system (PS). |
| The pressure for the leak test is 2–3 bar. |
140
Medium
What is temperature slip?
| A specific temperature corresponds to a given vapour pressure. |
| It involves a decrease in temperature. |
| It involves an increase in temperature. |
| A specific temperature cannot be assigned to a given vapour pressure. There is a temperature difference between the start and end of evaporation. |
141
Difficult
What does a vacuum leak test involve?
| If the pressure in the refrigeration system were to rise, we switch on the vacuum pump as required. |
| With the vacuum pump running continuously, we are able to maintain the required vacuum level in the system. |
| After switching off the vacuum pump, we check whether the pressure in the system rises |
| With the vacuum pump switched on, check whether the pressure in the system rises as a result of a leak. |
142
Difficult
How often should leak tests be carried out on equipment containing 1.5 kg of R404A refrigerant (5.9 tonnes of CO₂ equivalent)?
| Only when servicing the unit. |
| Once every six months. |
| On initial commissioning. |
| At least once every 12 months. |
143
Difficult
How often should leak tests be carried out on equipment containing 7 kg of R404A refrigerant (27.45 tonnes of CO₂ equivalent)?
| On initial commissioning. |
| At least once every 12 months. |
| Only when servicing the unit. |
| Once every six months. |
144
Medium
In which appliances and systems is the installation of a permanent leak detection system required?
| In equipment and systems containing at least 500 tonnes of CO₂ equivalent. |
| In equipment and installations containing at least 30 kg of fluorinated greenhouse gases. |
| In equipment and systems containing at least 5 tonnes of CO₂ equivalent. |
| In equipment and systems containing at least 50 tonnes of CO₂ equivalent. |
145
Difficult
In accordance with Regulation (EU) 2024/573 of the European Parliament and of the Council, a fixed leak detection system is required when:
| The refrigeration equipment is operated in an enclosed space. |
| The refrigerant charge of the refrigeration equipment is at least 100 kg of ODS. |
| The charge of an F-gas refrigerant in a refrigeration unit is at least 500 tonnes of CO₂ equivalent. |
| The installation of a fixed leak detection system is optional, but it helps to reduce the number of leak checks required on the equipment each year. |
146
Difficult
Under Regulation (EC) No 1516/2007 and the F-gas Act, which leak detection methods may not be carried out by a person holding a Category E certificate?
| Leak testing using a fluorescent dye. |
| Visual leak inspection. |
| Measuring leaks using a handheld leak detector. |
| Leak detection using a foaming solution. |
147
Difficult
According to the current regulation, what sensitivity must a handheld leak detector have?
| 10 g/year. |
| 3 g/year. |
| 8 g/year. |
| 5 g/year. |
148
Medium
Which category of F-gas certificate (A1, A2, B, C, D, E) authorises the performance of leak tests on refrigeration equipment:
| Category E only. |
| All except category D. |
| Only categories A1 and A2. |
| Categories D and E. |
149
Difficult
Within what timeframe must a leak test be carried out on a stationary refrigeration system after a leak has been repaired, in accordance with EU Regulation 2024/573 on F-gases?
| Immediately after the repair. |
| At the next periodic inspection. |
| Between 24 hours and 1 month after the repair. |
| At any time. |
150
Difficult
At what intervals should leak tests be carried out on refrigeration equipment containing more than 500 tonnes of CO₂ equivalent of fluorinated greenhouse gases that does not have a leak detection system installed?
| Once every 3 months. |
| Once every 12 months. |
| Once every 6 months. |
| Once a month. |
151
Medium
Why is it advisable to subcool the liquid refrigerant?
| This is advisable because it ensures that the liquid refrigerant, free of vapour bubbles, enters the expansion valve. |
| This is advisable because it allows a smaller condenser to be used (smaller heat exchange surface area). |
| This is advisable because it allows a smaller expansion valve to be used (less superheat at the valve). |
| This is advisable because it allows a smaller evaporator to be used (lower refrigerant temperature at the evaporator inlet). |
152
Medium
What should be done following repairs to a leak in the refrigeration unit of a refrigerated trailer?
| The unit must be charged with an alternative refrigerant, started up, and the refrigerant parameters checked at the service valve located on the liquid receiver. |
| A visual inspection should be carried out only on bolted and soldered joints. |
| An invoice for the service work carried out must be issued as soon as possible. |
| You must enter the details into the equipment log (including the quantities of refrigerant recovered and used) and inform the Operator that an additional leak test must be carried out by a certified person within one month of the repair. |
153
Medium
Recovery of fluorinated greenhouse gases means:
| The collection and storage of fluorinated greenhouse gases originating, for example, from machinery, equipment and containers. |
| The reprocessing of fluorinated greenhouse gases to achieve their specified standard properties. |
| The final decommissioning and withdrawal from service or use of a product or piece of equipment containing fluorinated greenhouse gases. |
| The reuse of fluorinated greenhouse gases following a basic purification process. |
154
Medium
Who is authorised to recover refrigerant from stationary refrigeration equipment:
| The owner of the installation. |
| The operator. |
| The administrator of the operator’s account. |
| A service technician holding an F-gas certificate in the relevant category. |
155
Medium
Recovered refrigerants must be stored:
| In a specially adapted and labelled cylinder fitted with a two-way valve. |
| In any pressure vessel that has been officially certified. |
| In a cylinder that previously contained the same type of refrigerant. |
| In any used refrigerant cylinder. |
156
Medium
When should the recovery of fluorinated greenhouse gases be carried out:
| Only prior to the final disposal of equipment. |
| Before each leak test of the equipment. |
| Before the final disposal of equipment and, where applicable, during its servicing and maintenance. |
| Always during servicing and maintenance of equipment. |
157
Medium
What should be done if the refrigerant recovered from the system is contaminated, e.g. with acid, air or moisture?
| You should attempt to purify the mixture yourself using a dehydrating filter. |
| Such a mixture must be handed over to a specialist authorised company for regeneration or disposal. |
| Purify the mixture by passing it through a particulate filter and reuse it. |
| Add a special contaminant neutraliser to the mixture. |
158
Medium
What should be done if different types of refrigerants become mixed in a storage cylinder (container)?
| Add a special refrigerant to the mixture. |
| The mixture should be purified by passing it through a filter-drain and reused. |
| Send this mixture to a specialist authorised company to have it neutralised. |
| You should attempt to separate the mixture into its individual components. |
159
Medium
How does refrigerant recovery using the Push-Pull method work?
| This involves the refrigerant being alternately drawn from the suction side and then from the discharge side of the refrigeration unit (compressor). |
| It involves using a recovery unit to draw (pull) the refrigerant vapour from the cylinder and then force it (push) into the low-pressure side of the system. |
| This involves injecting nitrogen from the cylinder into the unit and expelling the liquid refrigerant from the unit. |
| This involves using a suction device (compressor) to ensure that the refrigerant, in liquid form, is transferred into the cylinder. |
160
Medium
What are the methods for managing waste refrigerant?
| Disposal, storage. |
| Recovery, disposal. |
| Regeneration, recovery. |
| Recycling, regeneration, disposal. |
161
Medium
The most advantageous method of managing waste refrigerant is:
| Recycling. |
| Regeneration. |
| Storage. |
| Disposal. |
162
Medium
The lower the evaporation temperature, ...
| ...the greater the density of the refrigerant and the mass flow rate of the flowing refrigerant. |
| ...the lower the density of the refrigerant and the lower the mass of the flowing refrigerant. |
| ...the lower the refrigerant density, and the greater the cooling capacity of the compressor. |
| …the greater the density of the refrigerant and the lower the mass flow rate of the refrigerant. |
163
Medium
How should pressure vessels (e.g. refrigerant cylinders) be marked?
| They should bear only markings relating to weight and capacity. |
| They should bear the manufacturer’s logo and the date of manufacture. |
| They should bear, amongst other things, information such as: the number of the standard applied to their design, construction and testing; the identification marks of the country of approval and the inspection body; the date of the acceptance test; and the manufacturer’s and operational marks. |
| It is irrelevant how pressure vessels should be marked. |
164
Medium
The recovery of refrigerants does not require the use of:
| An electronic leak detector. |
| Scales with a measurement range suitable for the size of the cylinder being filled. |
| Hoses with shut-off valves. |
| A refrigerant recovery station. |
165
Medium
What functions does the compressor perform in a refrigeration system?
| The compressor condenses the refrigerant. |
| The compressor draws in refrigerant vapour from the evaporator, compresses it, and then forces it into the condenser, raising the pressure to the required condensing pressure. |
| The compressor compresses ambient air and increases the pressure of the refrigerant. |
| The compressor creates a vacuum on the suction side of the system |
166
Easy
What is the compressor’s compression ratio?
| It is the ratio of the discharge pressure to the effective capacity of the compressor (p/Vk). |
| It is the ratio of the suction pressure to the discharge pressure of the compressor (po/pk). |
| It is the ratio of the discharge pressure to the suction pressure of the compressor (pk/po). |
| It is the amount of refrigerant that will be compressed in a single compressor cycle relative to the heat capacity. |
167
Medium
What is compressor flooding?
| Flooding of the compressor due to rainfall. |
| Flooding the compression chamber with liquid refrigerant or oil. |
| A large amount of liquid refrigerant in the evaporator. |
| Suction of liquid refrigerant into the compressor’s suction line. |
168
Medium
To what extent do we regulate the compressor motor’s rotational speed when using a frequency converter?
| Up to a maximum of 10 per cent. |
| Regulating the compressor motor speed is not the same as regulating the cooling capacity. |
| Approximately from 30 to 75 Hz, which corresponds to around 60% to 150% of the cooling capacity. |
| From approximately 30% to 90% of capacity. |
169
Easy
What is the theoretical displacement of a compressor?
| This is the volume of refrigerant that flows through a reciprocating compressor during a single piston cycle. |
| The displacement of a compressor is determined by the dimensions of the cylinder – its volume (cm³) |
| It is the volume of refrigerant delivered by a reciprocating compressor per unit of time, usually referred to by the manufacturer as the displacement. It depends on the compressor’s geometric dimensions and rotational speed. |
| The displacement capacity of a compressor is expressed by the coefficient of performance (COP) |
170
Medium
Why is it essential to observe the correct phase sequence for scroll compressors and screw compressors?
| Because this type of compressor has difficulty starting up if the phase sequence is changed. |
| Because changing the phase sequence would reverse the direction of rotation of the compressor rotors, which could result in damage to the compressors. |
| Because the motor speed would decrease, and consequently the compressor’s capacity. |
| Because these types of compressors are sensitive to voltage drops. |
171
Medium
The cycle of a two-stage vapour-compression refrigeration system should have, in each stage of the system:
| a compression ratio of less than 6 |
| a compression ratio of less than 18. |
| a compression ratio of less than 8. |
| a compression ratio greater than 8. |
172
Medium
Why is it necessary to seal the shafts in gland-sealed refrigeration compressors?
| Because it protects the compressor’s crankshaft bearing. |
| Because it prevents oil leakage. |
| Because we need to prevent air from entering the compressor and we need to prevent refrigerant from leaking from the compressor. |
| Because it ensures the bearing remains lubricated. |
173
Medium
When is the refrigerant sufficiently cooled?
| When the outlet from the condenser is cold. |
| When no vapour bubbles are observed forming in the liquid sight glass. |
| When the liquid distributors are warm. |
| When the evaporator is covered in frost. |
174
Medium
Why should the compressor crankcase be heated?
| Heating improves the dissolution of the refrigerant in the oil, which is beneficial for its viscosity. |
| Heating ensures that the lubricating oil is de-watered. |
| Heating keeps the lubricating oil in a liquid state. |
| Heating prevents the refrigerant from dissolving in the oil. |
175
Easy
What is the dead volume of a compressor?
| This is the space between the side surface of the piston and the cylinder. |
| This is the space between the bottom of the piston and the crankshaft cover. |
| It is the space between the valve plate and the bottom dead centre of the piston. |
| It is the space between the valve plate and the top of the piston. |
176
Medium
What are compressor sets?
| These consist of a larger number (several) of compressors connected in parallel and mounted on a common frame. |
| These are units consisting of two-stage compressors. |
| These are multiple (several) air-cooled condensers. |
| These are sets comprising several compressors connected in any configuration. |
177
Medium
What are the advantages of compressor units?
| Space-saving and lower energy consumption. |
| Easy modification of the system. |
| The ability to adjust the cooling capacity as required. |
| These are inexpensive and easy-to-install units. |
178
Medium
What do we mean by the ‘application range’ of a compressor?
| By this term, we mean that the compressor’s application range is determined by the evaporation temperature ‘to’ at a given ambient temperature. |
| By this term, we mean that the compressor’s operating range is determined by the evaporation temperature ‘to’ during operation. |
| By this term, we mean the following parameters: the evaporation and condensation temperatures (to and tk), or the pressure values that determine the compressor’s application. |
| By this term, we mean the following parameters: compressor capacity, type of refrigerant, and the compressor’s geometric dimensions. |
179
Medium
What are the basic functions of oil in a compressor?
| The oil absorbs moisture from the refrigerant that enters the compressor. |
| The oil seals any leaks that develop in the system. |
| The oil lubricates both the bearings and the sliding surfaces of the compressor components, and cools the compressor by transferring the heat generated during compression to the compressor’s outer casing. |
| The oil seals the gap between the piston and the cylinder. |
180
Medium
What are the most effective ways of regulating the compressor’s cooling capacity?
| By partially covering the evaporator to reduce the heat exchange surface area. |
| Using an expansion valve. |
| By changing the compressor’s displacement, by varying the rotational speed, or by deactivating individual cylinders. |
| By means of pressure control valves. |
181
Medium
What does compressor bypass control involve?
| Refrigerant in the form of cooled, high-pressure vapour is introduced into the suction line. |
| The bypass control is not used to regulate the compressor. |
| Hot, high-pressure refrigerant vapour is drawn in on the suction side of the compressor. |
| High-pressure liquid refrigerant is injected on the suction side of the compressor. |
182
Medium
What is the fundamental difference between hermetic and semi-hermetic compressors?
| The casing of semi-hermetic compressors can be dismantled, whereas the casing of hermetic compressors cannot be dismantled. |
| The housing of a hermetic compressor and the compressor itself form a single unit. |
| Semi-hermetic compressors are characterised by the quiet operation of the entire unit. |
| Both types of compressors are disassemblable, and the difference lies in their varying capacities. |
183
Medium
How does a scroll compressor work?
| It is a device fitted with two spirals. It is a type of positive displacement (volumetric) compressor in which compression takes place through the interaction of the two spirals. |
| It is a type of piston-type device. |
| It uses two screws to compress the refrigerant. |
| A scroll compressor is also known as a turbo compressor. |
184
Medium
What physical process takes place in the evaporator?
| The liquid refrigerant evaporates and a small amount of it becomes superheated. |
| It causes the refrigerant flowing through it to condense. |
| It cools the refrigerant flowing through it. |
| The medium flowing through the evaporator (glycol, water) evaporates, whilst the refrigerant condenses. |
185
Medium
What is the purpose of regulating the compressor’s capacity?
| It ensures that the cooling capacity is adjusted based on condensing temperatures. |
| It ensures adequate lubrication of the compressor. |
| Capacity control protects the compressor from low thermal loads. |
| It allows the cooling capacity to be adjusted to meet requirements. |
186
Medium
Why is inverter speed control suitable for refrigeration compressors?
| By reducing the speed of the refrigeration compressor motor, inverter speed control improves the return oil flow to the compressor. |
| Inverter speed control can be used with any type of compressor to ensure adequate lubrication. |
| Inverter speed control enables continuous, smooth regulation of cooling capacity. |
| Inverter speed control reduces energy consumption only under natural conditions. |
187
Medium
Does the suction gas temperature affect the cooling capacity of the compressor?
| It does, but only if the gas is deeply cooled. |
| It has a significant effect on performance. |
| It does, but only for reciprocating compressors. |
| Temperature has no effect on the compressor’s cooling capacity. |
188
Medium
In the case of compressor units fitted with an oil level control system, is it necessary to install the compressors at the same height?
| Only scroll compressors. |
| Yes. |
| Only screw compressors. |
| No. |
189
Medium
What functions does a compressor powered by the vehicle’s engine perform in a transport refrigeration system?
| This compressor creates a vacuum on the suction side of the system whilst the vehicle’s engine is switched off. |
| This compressor draws in refrigerant vapour from the evaporator, compresses it and then forces it into the condenser whilst the vehicle’s engine is running. |
| This compressor condenses the refrigerant whilst the vehicle is in motion. |
| The compressor compresses ambient air and increases the pressure of the refrigerant. |
190
Medium
Which natural fluids absorb heat from the refrigerant in the condenser?
| Water or air. |
| Ammonia |
| Water and an antifreeze mixture. |
| Air and CO2. |
191
Medium
What is the function of the condenser in refrigeration systems?
| Heat from the compressor is then released into the environment via the condenser. |
| Heat released in the regenerative heat exchanger is absorbed by the condenser. |
| The heat absorbed in the evaporator is then released into the environment via the condenser |
| The heat absorbed in the evaporator and transferred during the compression process is then released into the environment via the condenser. |
192
Medium
If the condensation temperature is higher than the critical point temperature of the refrigerant, condensation:
| will occur provided a specially designed condenser is used. |
| will not occur. |
| temperature has no effect on condensation. |
| will always occur regardless of the temperature. |
193
Medium
How does the subcooling of the refrigerant take place within a refrigeration system?
| Subcooling using high-pressure hot vapour. |
| Subcooling of the liquid refrigerant in the final section of the condenser. |
| Subcooling of the refrigerant using oil (dissolving the refrigerant in oil). |
| Subcooling using an additional heat exchanger and liquid nitrogen. |
194
Medium
What is the purpose of controlling the condenser fan speed?
| Condenser fan speed control reduces energy efficiency. |
| Condenser fan speed control ensures that the condensing pressure is maintained at the correct level. |
| Condenser fan speed control safeguards against the maximum permissible condensing pressure. |
| Dispersion of the refrigerant in the event of a system leak. |



